Inspections for the day of: Wednesday, May 1, 2013.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-00021 FIRE-Final Inspection4/30/20135/1/20135/1/2013 3:53:38 PMAFAIL
Waiting for fire dept approval of the exiting from the phase of construction dated "5/3" and highlighted in purple. This area is to the immediate west of the call center.
BLD13-00997 FIRE-Final Inspection4/29/20135/1/20135/1/2013 3:44:23 PMACANC
Per Roy correctioh items have not been completed. He will reschedule.
BLD12-00382 FIRE-Conference4/30/20135/1/20135/1/2013 3:27:44 PMPDONE
Mike and I wnet over life safety requirements in the Lexus showroom, upper and lower mezzanine and the Sales Bull Pen.
FIR12-00670 INSP-Sprinkler Rough-in4/30/20135/1/20135/1/2013 2:38:21 PMAPASS
All piping can be covered except the south "east/west" corridor and southeast room. Head installation is not complete in these two areas. Also additional sprinkler coverage will be required in the "electrical room" due to a half ceiling being installed. Also two additional dry pendants will be required behind the condensor units in the cooler.
BLD13-01000 FIRE-Final Inspection4/30/20135/1/20135/1/2013 10:42:28 AMAFAIL
Remove the thumbturn dead bolts from all four exterior exit doors. Keyed hardware on egress side is ok on two of the doors as per plan. Provide single action lever hardware on three of the four doors if lever hardware is desired (fourth door lever functions correctly). Provide stickers at the two keyed doors. As per discussion removing all of the dead bolts and just utilizing single action hardware is an option as well.
BLD13-00529 FIRE-Final Inspection4/30/20135/1/20135/1/2013 9:31:18 AMAPASS
Life safety passed. Directional arrow on west exit sign needs punched out so people are not led to the locked door prior to the building inspection
BLD13-00416 FIRE-Final Inspection4/30/20135/1/20135/1/2013 7:21:19 AMAPASS
Life safety passed
FIR12-00670 INSP-Sprinkler Rough-in/Hydro4/29/20135/1/20134/30/2013 11:27:25 AMPCANC
Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus