ELE12-00814
| ELE-Aging Inspection | 5/1/2015 | 5/1/2015 | 5/1/2015 3:35:11 PM | | DONE |
|
|
Waiting on contractor
|
ELE12-02127
| ELE-Aging Inspection | 5/1/2015 | 5/1/2015 | 5/1/2015 3:32:58 PM | | DONE |
|
|
Waiting on contractor
|
ELE15-01222
| Final | 5/1/2015 | 5/1/2015 | 5/1/2015 3:31:14 PM | P | CANC |
|
|
###-#### I created no call back
|
ELE15-00801
| Final | 5/1/2015 | 5/1/2015 | 5/1/2015 3:29:30 PM | P | PASS |
|
|
would like call ahead; George Phone #: ###-#### T squared out of Utah. Thaniel Bishop contractor # C-18933. 2169 W. 8910 S. West jordan Utah 84088. Final ok
|
ELE15-00801
| Electrical Rough-In | 5/1/2015 | 5/1/2015 | 5/1/2015 3:26:57 PM | P | PASS |
|
|
would like call ahead; George Phone #: ###-#### UL listings confirmed Rough in ok.
|
ELE15-01117
| Final | 5/1/2015 | 5/1/2015 | 5/1/2015 3:16:51 PM | P | FAIL |
|
|
would like call ahead; George Phone #: ###-#### T-Squared out of Utah. Thaniel Bishop contractor # C-18933. 2169 W.8910 S. West Jordan Utah 84088. 300.3(B)- All conductors of same circuit shall be installed in a conduit or cable system recognized by this artical.
|
ELE15-01266
| Final | 5/1/2015 | 5/1/2015 | 5/1/2015 2:01:29 PM | P | PASS |
|
|
Robert Phone #: ###-#### Final ok
|
ELE15-01266
| Electrical Rough-In | 5/1/2015 | 5/1/2015 | 5/1/2015 2:01:19 PM | P | PASS |
|
|
Robert Phone #: ###-#### Heat pump rough in ok
|
ELE15-01265
| Final | 5/1/2015 | 5/1/2015 | 5/1/2015 1:44:48 PM | P | PASS |
|
|
Robert Phone #: ###-#### Final ok
|
ELE15-01265
| Electrical Rough-In | 5/1/2015 | 5/1/2015 | 5/1/2015 1:44:37 PM | P | PASS |
|
|
Robert Phone #: ###-#### Heat pump rough in ok
|
ELE15-01267
| Final | 5/1/2015 | 5/1/2015 | 5/1/2015 1:24:22 PM | P | NH |
|
|
Call for access Brian Robertson ###-#### Phone #: ###-#### Inspection requested via web by jamie berg No answer at door and no return phone call left message
|
ELE15-01232
| Permanent Service | 4/30/2015 | 5/1/2015 | 5/1/2015 1:10:39 PM | P | PASS |
|
|
Inspection of service change for reconnect by Idaho Power Phone #: ###-#### Inspection requested via web by Rick Beckman p/s o/h rec ok
|
ELE15-00692
| Final | 5/1/2015 | 5/1/2015 | 5/1/2015 12:48:55 PM | P | PASS |
|
|
Please call 15 min. ahead so that I can be there or make sure that the homeowner is there. Thanks, Mark Estep Phone #: ###-#### Inspection requested via web by Mark Estep Final ok
|
ELE15-01273
| Permanent Service | 5/1/2015 | 5/1/2015 | 5/1/2015 12:29:46 PM | P | PASS |
|
|
George Phone #: ###-#### As per Daryl Degrange if no violations on existing service permitting ok by non contractor. p/s o/h rec ok
|
ELE15-01273
| Final | 5/1/2015 | 5/1/2015 | 5/1/2015 12:29:32 PM | P | PASS |
|
|
George Phone #: ###-#### Service reconnect final ok
|
ELE15-01222
| Final | 5/1/2015 | 5/1/2015 | 5/1/2015 11:21:12 AM | P | FAIL |
|
|
As early as possible would be great! Thank you..... Phone #: ###-#### Inspection requested via web by Krista Ratterree 310.15(B)(16)- #10 THHN protected by 100 amp breaker 30 amp max. #8 THHN protected by 60 amp breaker 50 amp max. 408.30(D)- Back fed over curent device shall be secured in place by additional fastener.
|
GCE15-00071
| GCE-Rough-In | 4/30/2015 | 5/1/2015 | 5/1/2015 10:28:01 AM | A | PASS |
|
|
Brian ###-#### Reception and fireplace walls rough in ok cover
|
GCE15-00069
| GCE-Rough-In Permanent Service | 4/30/2015 | 5/1/2015 | 5/1/2015 10:21:58 AM | A | PASS |
|
|
Rowdy ###-#### Rough in ok cover p/s u/g n ok
|
ELE15-01212
| Temporary Service | 4/30/2015 | 5/1/2015 | 5/1/2015 10:07:24 AM | A | PASS |
|
|
Temp Pole Inspection Phone #: ###-#### Inspection requested via web by Rowdy Monroe t/s u/g n ok
|
ELE15-01206
| Electrical Rough-In | 4/30/2015 | 5/1/2015 | 5/1/2015 9:18:53 AM | A | PART |
|
|
Pls. call Kyle Little 30 minutes before arrival at ###-#### Phone #: ###-#### Inspection requested via web by MIKE HAGERTY Walls except panel wall and soffits. 110.26(A)- Work space shall be provided for service disconnecting means of 36" deep and 30" wide minimum. 110.26(E)- Dedicated equipment space shall be clear up to 6' above panel location width and depth of panels. Areas noted rough in ok cover
|
ELE15-00712
| Final | 5/1/2015 | 5/1/2015 | 5/1/2015 8:45:44 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Final ok
|