Inspections for the day of: Friday, May 1, 2015.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00814 ELE-Aging Inspection5/1/20155/1/20155/1/2015 3:35:11 PM DONE
Waiting on contractor
ELE12-02127 ELE-Aging Inspection5/1/20155/1/20155/1/2015 3:32:58 PM DONE
Waiting on contractor
ELE15-01222 Final5/1/20155/1/20155/1/2015 3:31:14 PMPCANC
###-#### I created no call back
ELE15-00801 Final5/1/20155/1/20155/1/2015 3:29:30 PMPPASS
would like call ahead; George Phone #: ###-#### T squared out of Utah. Thaniel Bishop contractor # C-18933.
2169 W. 8910 S. West jordan Utah 84088. Final ok
ELE15-00801 Electrical Rough-In5/1/20155/1/20155/1/2015 3:26:57 PMPPASS
would like call ahead; George Phone #: ###-#### UL listings confirmed Rough in ok.
ELE15-01117 Final5/1/20155/1/20155/1/2015 3:16:51 PMPFAIL
would like call ahead; George Phone #: ###-#### T-Squared out of Utah. Thaniel Bishop contractor # C-18933. 2169 W.8910 S. West Jordan Utah 84088. 300.3(B)- All conductors of same circuit shall be installed in a conduit or cable system recognized by this artical.
ELE15-01266 Final5/1/20155/1/20155/1/2015 2:01:29 PMPPASS
Robert Phone #: ###-#### Final ok
ELE15-01266 Electrical Rough-In5/1/20155/1/20155/1/2015 2:01:19 PMPPASS
Robert Phone #: ###-#### Heat pump rough in ok
ELE15-01265 Final5/1/20155/1/20155/1/2015 1:44:48 PMPPASS
Robert Phone #: ###-#### Final ok
ELE15-01265 Electrical Rough-In5/1/20155/1/20155/1/2015 1:44:37 PMPPASS
Robert Phone #: ###-#### Heat pump rough in ok
ELE15-01267 Final5/1/20155/1/20155/1/2015 1:24:22 PMPNH
Call for access Brian Robertson ###-#### Phone #: ###-#### Inspection requested via web by jamie berg No answer at door and no return phone call left message
ELE15-01232 Permanent Service4/30/20155/1/20155/1/2015 1:10:39 PMPPASS
Inspection of service change for reconnect by Idaho Power Phone #: ###-#### Inspection requested via web by Rick Beckman p/s o/h rec ok
ELE15-00692 Final5/1/20155/1/20155/1/2015 12:48:55 PMPPASS
Please call 15 min. ahead so that I can be there or make sure that the homeowner is there.
Thanks,
Mark Estep Phone #: ###-#### Inspection requested via web by Mark Estep Final ok
ELE15-01273 Permanent Service5/1/20155/1/20155/1/2015 12:29:46 PMPPASS
George Phone #: ###-#### As per Daryl Degrange if no violations on existing service permitting ok by non contractor. p/s o/h rec ok
ELE15-01273 Final5/1/20155/1/20155/1/2015 12:29:32 PMPPASS
George Phone #: ###-#### Service reconnect final ok
ELE15-01222 Final5/1/20155/1/20155/1/2015 11:21:12 AMPFAIL
As early as possible would be great! Thank you..... Phone #: ###-#### Inspection requested via web by Krista Ratterree 310.15(B)(16)- #10 THHN protected by 100 amp breaker 30 amp max. #8 THHN protected by 60 amp breaker 50 amp max.
408.30(D)- Back fed over curent device shall be secured in place by additional fastener.
GCE15-00071 GCE-Rough-In4/30/20155/1/20155/1/2015 10:28:01 AMAPASS
Brian ###-#### Reception and fireplace walls rough in ok cover
GCE15-00069 GCE-Rough-In Permanent Service4/30/20155/1/20155/1/2015 10:21:58 AMAPASS
Rowdy ###-#### Rough in ok cover p/s u/g n ok
ELE15-01212 Temporary Service4/30/20155/1/20155/1/2015 10:07:24 AMAPASS
Temp Pole Inspection Phone #: ###-#### Inspection requested via web by Rowdy Monroe t/s u/g n ok
ELE15-01206 Electrical Rough-In4/30/20155/1/20155/1/2015 9:18:53 AMAPART
Pls. call Kyle Little 30 minutes before arrival at ###-#### Phone #: ###-#### Inspection requested via web by MIKE HAGERTY Walls except panel wall and soffits. 110.26(A)- Work space shall be provided for service disconnecting means of 36" deep and 30" wide minimum.
110.26(E)- Dedicated equipment space shall be clear up to 6' above panel location width and depth of panels.
Areas noted rough in ok cover
ELE15-00712 Final5/1/20155/1/20155/1/2015 8:45:44 AMAPASS
Phone #: ###-#### Inspection requested via web by Greg Traudt Final ok