Inspections for the day of: Monday, May 1, 2017.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03147 Conference5/1/20175/1/20175/1/2017 3:12:23 PMPDONE
Shane ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
Discussed wiring method for relocated cabinets and chairs. Cabinets have been rewired and need to be field evaluated by 3rd party listing company or certified electrical engineer as per Boise City Ordinance and UL guide lines. Medical equipment must be rebuilt or refurbished by original manufacturer or certified company who specialize in this type of equipment.
ELE17-00769 Electrical Rough-In4/28/20175/1/20175/1/2017 12:56:24 PMAPASS
Branch panel and transformer inspection. Feeder cables.
Contact is Kenny Williams ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves
Transformer, feeders, clouds rough in ok
ELE17-01009 Conference4/27/20175/1/20175/1/2017 11:56:27 AMADONE
Please contact Ryan ###-#### on-site Phone #: ###-#### Inspection requested via web by Tracy Robertson
Discussed fixed panel in unit B-1 on sliding door in a hall or walkway so receptacle not required for 2' of greater wall space.
Number of 1 required receptacle for islands without divided space and overhangs causing conflict.
SER ampacity using 2017 code 83% of rating of overcurrent device.
ELE17-01260 Temporary Service4/30/20175/1/20175/1/2017 11:51:42 AMAPASS
Temp Service Inspection Underground service
Phone #: ###-#### Inspection requested via web by Don Conley
t/s u/g n ok
ELE17-01257 Rough-In Permanent Service4/30/20175/1/20175/1/2017 11:50:54 AMAFAIL
Phone #: ###-#### Inspection requested via web by Therrin Robertson
210.52(A)- Arbor room enclosed need general layout for habitable room. Discussed at meeting with other inspectors and ruled if only used for green house purposes general receptacles not required however if finished sunroom type room 210.52(A) will be enforced.
300.4- NM cable shall be protected from damage where run thru bored holes that do not maintain 1 1/4" from framing surface.
352.6- All PVC pipe and fittings shall be listed. 2" expansion joint (Cantex 1 piece) not listed