ELE18-01642
| Conference | 5/1/2018 | 5/1/2018 | 5/1/2018 4:04:38 PM | P | DONE |
|
|
Justin Phone #: ###-#### Discussed the replacement of a panel in one shop and sub-feeding another shop. A 200 amp 40 circuit main breaker panel going in green shop and a 100 amp sub to 2nd shop. Concrete encased electrode exists in green shop, 2nd shop will need 2 ground rods 6' or more apart. Discussed wire sizes and types of wiring meathods for underground, burial depth, and disconnecting means for each structure.
|
ELE18-01636
| Electrical Rough-In | 5/1/2018 | 5/1/2018 | 5/1/2018 2:42:29 PM | P | PASS |
|
|
not much to see but would like you to have a look before ask for final Phone #: ###-#### Inspection requested via web by dennis mcneely Serving counter offering teas and shakes no cooking. Owner installed lighting with festoon look on line volt cable and secured with metal straps, asked to replace with plastic straps. Rough in ok cover
|
ELE18-01634
| Conference | 5/1/2018 | 5/1/2018 | 5/1/2018 2:09:59 PM | P | DONE |
|
|
Phone #: ###-#### Inspection requested via web by David McClellan Discussed scope of work on old house which will be a rental. Scope of work is up bath and kitchen remodel. All exposed knob and tube wiring will be removed as requested by owner. no wells to be opened up except up bath and kitchen area. Perimeter walls concrete so may surface mount conduits to required kitchen receptacles. Adding smoke detectors and will fix all life safety issues in basement. Open splice upper attic closet will be repaired.
|
ELE18-01195
| Electrical Rough-In | 5/1/2018 | 5/1/2018 | 5/1/2018 1:24:28 PM | P | FAIL |
|
|
Ceiling inspection please. Have a bless week! Phone #: ###-#### Inspection requested via web by Kyle Lott 110.14- Splice points shall be accessible. 2 boxes located above clouds. 300.4- MC shall be secured 1 1/4" from framing surface. 314.23- Boxes hanging out of cloud shall be securely mounted to structure.
|
ELE18-00590
| Final | 4/30/2018 | 5/1/2018 | 5/1/2018 11:18:17 AM | A | PASS |
|
|
garage code 4218 Phone #: ###-#### Inspection requested via web by kevin blackmon Final ok
|
ELE18-01330
| Electrical Rough-In | 4/30/2018 | 5/1/2018 | 5/1/2018 10:34:10 AM | A | PASS |
|
|
Please call 30min in advance to ensure access. Phone #: ###-#### Inspection requested via web by Casey Fouts Check above grid for open boxes or old luminaires. Walls rough in ok cover
|
ELE18-01506
| Final | 4/30/2018 | 5/1/2018 | 5/1/2018 9:58:36 AM | A | PASS |
|
|
requests after 9 AM - Michael Phone #: ###-#### Final ok
|
ELE18-00408
| Electrical Rough-In | 4/30/2018 | 5/1/2018 | 5/1/2018 9:50:21 AM | A | PASS |
|
|
We need a wall cover inspection, thank you. Dustin is your on-site contact and can be reached at 208.293.4442. Phone #: ###-#### Inspection requested via web by Stacie Tasker Underground not metallic. Reception area 1/2 walls non patient care rough in ok cover
|
ELE18-01286
| Temporary Service | 4/30/2018 | 5/1/2018 | 5/1/2018 9:05:01 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas t/s u/g n ok
|
ELE18-01288
| Temporary Service | 4/30/2018 | 5/1/2018 | 5/1/2018 9:04:27 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas t/s u/g n ok
|
ELE18-01620
| Temporary Service | 4/30/2018 | 5/1/2018 | 5/1/2018 9:03:48 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas t/s u/g n ok
|
ELE18-01621
| Temporary Service | 4/30/2018 | 5/1/2018 | 5/1/2018 9:03:07 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas t/s u/g n ok
|