Inspections for the day of: Tuesday, May 1, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-04550 FIRE-Final Inspection4/30/20185/1/20185/1/2018 6:44:44 PMAFAIL
Provide fire extinguisher with a current inspection tag.

Zak Phone #: ###-####
BLD18-00470 FIRE-Final Inspection4/30/20185/1/20185/1/2018 2:40:18 PMPFAIL
Provide single action door hardware on main entry, current paddle hardware does not operate when locked. Provide sticker on main entry reading "Door to remain unlocked while occupied". Fire extinguisher needs to be inspected and tagged accordingly.
BLD16-01058 FIRE-Final Inspection4/30/20185/1/20185/1/2018 2:28:57 PMPPART
Partial life fire safety inspection for tco complete (30 day TCO per conversation with Ron Johnson) Fire sprinkler inspection complete, fire alarm inspection complete, fire exitnguishers are in place and will get inspection tags installed before final inspection. Items that need to be completed before final is a knox box installed by front entry and emergency evacuation plan for each unit, items will be verified before final C of O
FIR16-00473 INSP-Final Inspection5/1/20185/1/20185/1/2018 1:44:15 PMPPASS
Final underground supply inspection complete.
FIR17-00730 INSP-Final Inspection5/1/20185/1/20185/1/2018 12:17:03 PMPPASS
Final fire sprinkler inspection complete.
FIR18-00168 INSP-Final Inspection4/30/20185/1/20185/1/2018 10:53:17 AMAFAIL
AES communicator is not within 20 feet of the fire as noted on the city approved drawings. AES communicator is not on a dedicated circuit.
FIR18-00293 INSP-Final Inspection4/30/20185/1/20185/1/2018 10:17:55 AMAPASS
Final fire sprinkler inspection for area of work complete.
FIR18-00231 INSP-Final Inspection5/1/20185/1/20185/1/2018 10:15:14 AMAPASS
Final fire sprinkler inspection complete
BLD17-03533 FIRE-Final Inspection4/30/20185/1/20185/1/2018 9:51:50 AMAPART
Partial final inspection complete, no fire sprinklers, no fire alarm modifications, fire extinguishers are in place with current inspection tags, box needs to be built for roll up door for heat collection on fusible link, life fire safety can be finaled when box is complete.