Inspections for the day of: Monday, May 10, 2004.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00251 INSP-Sprinkler Rough-in/Hydro5/10/20045/10/20045/10/2004 12:00:00 AMAFAIL
Provide access into the fire sprinkler riser room for verification of annual inspection tag on riser and verification of sprinkler monitoring. Provide verification that the anti-freeze loop located in this space has annual inspection. Provide electonic monitoring of the control valve for the anti-freeze loop by the fire alarm panel. This work will require a permit. Test the modified portion of the sprinkler system per review note #35. Sprinkler piping is ok to cover. 5/10/2004 9:54:38 AM
BLD04-00788 FIRE-Final Inspection5/10/20045/10/20045/10/2004 12:00:00 AMPPASS
fire life safety finaled 5/10/2004 2:46:50 PM