Inspections for the day of: Tuesday, May 10, 2005.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS04-00319 FIR-Final5/10/20055/10/20055/10/2005 3:29:09 PMPFAIL
Fire extinguisher has not yet been moved to a normal path of travel as noted by previous inspection on 3/9/05. Notified tenant of requirements for this issue to be resolved.
BLD04-02505 FIRE-Sprinkler Rough-in5/9/20055/10/20055/10/2005 1:56:21 PMACANC
sunny; Phone #: ###-#### Cancel inspection, called in under the wrong permit type.
BLD03-02056 FIRE-Final Inspection5/9/20055/10/20055/10/2005 9:57:20 AMAPASS
Fire life safety finaled.
BLD03-02056 FIRE-Alarm Testing5/9/20055/10/20055/10/2005 9:55:37 AMAPASS
Fire alarm passed inspection.
FIR04-00237 INSP-Final Inspection5/9/20055/10/20055/10/2005 9:48:05 AMAPASS
Fire sprinkler finaled.
FIR04-00593 INSP-Sprinkler Rough-in/Hydro5/9/20055/10/20055/10/2005 9:07:59 AMAPART
Begin 24 hour air test of preaction system at 9:00 am on 5/10/05.
FIR04-00387 INSP-Final Inspection5/10/20055/10/20055/10/2005 12:00:00 AMAPASS
Fire alarm finaled.
FIR05-00062 INSP-Sprinkler Rough-in/Hydro5/10/20055/10/20055/10/2005 12:00:00 AMPFAIL
Hanger on 1" arm over at end of 2" main, north side, is not within 2' of the end. Pendent head in soffit hard lid at corner is not installed as shown on plan. EQ brace on relocated 2 1/2" main is not installed on the last piece of main as shown on plan.