Inspections for the day of: Wednesday, May 10, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-00301 ELE-Aging Inspection5/10/20065/10/20065/12/2006 2:55:44 PM DONE
nr,suc
ELE06-00287 Final5/10/20065/10/20065/10/2006 4:28:02 PMPPASS
gene ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final
ELE06-01373 Electrical Rough-In5/10/20065/10/20065/10/2006 3:55:31 PMPNH
jeff or 3362961///request after 3 pm; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa nobody home, left sticker, neighbor said we could look in back, called owner, left message, told him to call me because he sounded like he was at a work place rather than working on house. from what I could see, he was not ready with make-up and outlet spacing.
ELE05-01642 ELE-Aging Inspection5/10/20065/10/20065/10/2006 3:38:25 PM DONE
called contr, he needs to see about a credit for this permit and then void out permit
ELE05-04481 Final5/10/20065/10/20065/10/2006 2:58:19 PMPPASS
gene ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final
ELE06-01647 Temporary Service5/10/20065/10/20065/10/2006 2:45:02 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dan Rohl t/s u/g n ok
ELE05-00537 ELE-Aging Inspection5/10/20065/10/20065/10/2006 2:05:48 PM DONE
suc
ELE05-03732 Final5/10/20065/10/20065/10/2006 1:36:19 PMPPASS
robert --call 1st for access ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called owner, left survey,nec 352(A) rnc shall be strapped within 3' of box or fitting, 408.4 circuit directory shall be clear concise and distinguished from other circuits, ok to final
ELE05-02615 Final5/9/20065/10/20065/10/2006 1:00:15 PMAPASS
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL ok to final
ELE06-01207 Electrical Rough-In5/10/20065/10/20065/10/2006 11:44:59 AMAPASS
EQUIPOTENTIAL GRID; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok to pour
ELE06-01580 Rough-In Permanent Service5/8/20065/10/20065/10/2006 10:44:25 AMAFAIL
Scheduled by a contractor via Hello! on 5/8/2006 at 9:09:47 PM. Contact: ###-####. called contr, left message, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection,210.52(H) recpt shall be in hall over 10', 210.63 recpt shall be within 25' of a/c, BCC all make-up shall be done
ELE06-01349 Final5/9/20065/10/20065/10/2006 10:10:09 AMAPASS
Scheduled by a contractor via Hello! on 5/9/2006 at 3:27:39 PM. Contact: ###-####. ok to final
ELE06-01078 Conference5/9/20065/10/20065/10/2006 9:41:03 AMADONE
richard; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles talked about replace feeder to new shop
ELE06-00671 Electrical Rough-In5/9/20065/10/20065/10/2006 9:12:55 AMAPART
Scheduled by a contractor via Hello! on 5/9/2006 at 1:14:42 PM. Contact: ###-####. ok to cover 3" cond, north side bldg
ELE06-01627 Electrical Rough-In5/9/20065/10/20065/10/2006 8:48:34 AMAPASS
Re-inspection; Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok to pour gec
ELE06-01314 Electrical Rough-In5/9/20065/10/20065/10/2006 8:10:07 AMAPASS
dick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles walls only ok to cover