BLD05-01287
| BLD-Aging Inspection | 5/10/2006 | 5/10/2006 | 5/17/2006 2:45:44 PM | | FAIL |
|
|
Outside storage still needs to be reduce to less than 12' and signage or chains limiting the maximum storage height inside to 22'-0"
|
FIR05-00665
| INSP-Final Inspection | 5/10/2006 | 5/10/2006 | 5/10/2006 4:52:28 PM | P | FAIL |
|
|
Contractor not ready for inspection due to cordination issues with locking the doors down for testing
|
FIR06-00062
| INSP-Final Inspection | 5/8/2006 | 5/10/2006 | 5/10/2006 3:59:35 PM | P | FAIL |
|
|
Relocate the grill to meet the 6" rule for hood coverage and demo the electrical outlet that does not shunt off. Provide final documentation.
|
BLD05-01860
| FIRE-Final Inspection | 5/10/2006 | 5/10/2006 | 5/10/2006 3:11:47 PM | P | PASS |
|
|
Life safety finaled. Curbing has been modified.
|
FIR05-00895
| INSP-Final Inspection | 5/10/2006 | 5/10/2006 | 5/10/2006 2:04:57 PM | P | PASS |
|
|
permit finaled
|
FIR06-00079
| INSP-Final Inspection | 5/9/2006 | 5/10/2006 | 5/10/2006 1:05:14 PM | P | PASS |
|
|
permit finaled
|
BLD06-00764
| FIRE-Final Inspection | 5/9/2006 | 5/10/2006 | 5/10/2006 12:43:31 PM | A | FAIL |
|
|
Repair the west exit sign, the sprinkler pendant located in the corridor in front of the restrooms is overspaced, provide one fire extinguisher, provide maximum occupant load sign.
|
FIR06-00209
| INSP-Sprinkler Rough-in/Hydro | 5/9/2006 | 5/10/2006 | 5/10/2006 12:21:35 PM | A | PASS |
|
|
Permit finaled
|
BLD06-00739
| FIRE-Final Inspection | 5/9/2006 | 5/10/2006 | 5/10/2006 11:26:25 AM | A | PASS |
|
|
Life safety finaled
|
FIR06-00230
| INSP-Final Inspection | 5/10/2006 | 5/10/2006 | 5/10/2006 11:25:56 AM | P | PASS |
|
|
Permit finaled
|
FIR06-00230
| INSP-Sprinkler Rough-in/Hydro | 5/9/2006 | 5/10/2006 | 5/10/2006 11:22:51 AM | A | PASS |
|
|
Fire sprinkler permit finaled
|
FIR06-00041
| INSP-Supply line flush | 5/9/2006 | 5/10/2006 | 5/10/2006 10:51:27 AM | A | PASS |
|
|
Underground flush passed.
|
FIR06-00325
| INSP-Final Inspection | 5/9/2006 | 5/10/2006 | 5/10/2006 10:28:10 AM | A | PASS |
|
|
Fire sprinkler permit finaled
|
FIR06-00249
| INSP-Final Inspection | 5/9/2006 | 5/10/2006 | 5/9/2006 5:13:06 PM | A | CANC |
|
|
fire sprinkler final; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung Disp set to [CANC] by a contractor via Hello! on May 9 2006 5:13PM.
|
BLD06-00573
| FIRE-Final Inspection | 5/9/2006 | 5/10/2006 | 5/9/2006 5:11:50 PM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung Disp set to [CANC] by a contractor via Hello! on May 9 2006 5:11PM.
|