Inspections for the day of: Thursday, May 10, 2007.
Number of inspections: 28
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00886 FIR-Aging Inspection5/10/20075/10/20075/16/2007 2:30:08 PM DONE
Work in progress.
BLD06-02628 FIRE-Final Inspection5/8/20075/10/20075/11/2007 3:40:20 PMAPASS
Fire life safety inspection passed.
BLD06-02256 FIRE-Final Inspection5/8/20075/10/20075/11/2007 3:33:13 PMAPASS
Fire life safety finaled.
BLD06-03343 FIRE-Final Inspection5/9/20075/10/20075/11/2007 11:55:58 AMAPASS
Corrections verified, fire life safety finaled.
FIR07-00072 INSP-Alarm Testing5/8/20075/10/20075/11/2007 9:07:15 AMPPASS
Fire alarm testing passed.
FIR07-00228 INSP-Sprinkler Rough-in/Hydro5/8/20075/10/20075/11/2007 9:05:01 AMAPART
OH rough-in and hydrostatic test both passed inspection.
BLD06-02628 FIRE-Alarm Testing5/8/20075/10/20075/10/2007 4:44:05 PMAPASS
Phone #: ###-#### Internet Inspection Request from: Rob Puckett
BLD06-02256 FIRE-Alarm Testing5/8/20075/10/20075/10/2007 4:43:37 PMAPASS
Phone #: ###-#### Internet Inspection Request from: Rob Puckett
FIR06-00689 INSP-Final Inspection5/8/20075/10/20075/10/2007 4:42:04 PMAPASS
Fire alarm permit finaled.
FIR06-00689 INSP-Alarm Testing5/8/20075/10/20075/10/2007 4:41:26 PMAPASS
Fire alarm work tested satisfactory.
FIR06-00595 INSP-Alarm Testing5/9/20075/10/20075/10/2007 4:35:44 PMACANC
don; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
MIS07-00103 FIR-Final5/10/20075/10/20075/10/2007 4:34:39 PMPPASS
Life safety acceptable.
MIS07-00102 FIR-Final5/10/20075/10/20075/10/2007 4:33:14 PMPPASS
Life safety finaled.
MIS07-00101 FIR-Final5/10/20075/10/20075/10/2007 4:32:06 PMPPASS
Life safety passed inspection.
BLD07-00340 FIRE-Final Inspection5/9/20075/10/20075/10/2007 4:31:00 PMAPASS
Fire life safety passed.
FIR07-00120 INSP-Final Inspection5/9/20075/10/20075/10/2007 4:30:02 PMAPASS
Fire alarm syst. corrections complete, inspection passed, permit finaled.
FIR07-00192 INSP-Final Inspection5/9/20075/10/20075/10/2007 4:28:16 PMAPASS
Fire sprinkler permit finaled.
FIR07-00362 INSP-Final Inspection5/9/20075/10/20075/10/2007 4:26:22 PMPPASS
Fire sprinkler work passed inspection, permit finaled.
BLD06-02729 FIRE-Final Inspection5/9/20075/10/20075/10/2007 12:39:19 PMAFAIL
Provide one additional PFE for the kitchen area and mount the remaining fire extinguishers as discussed, remove manual thumbturn lock at the SE employee restroom, provide missing emergency lighting for the metro coffee shop, remove one exit sign as agreed.
FIR07-00240 INSP-Final Inspection5/9/20075/10/20075/10/2007 11:37:57 AMAPASS
Final FS permit inspection passed, corrections complete.
FIR07-00286 INSP-Final Inspection5/8/20075/10/20075/10/2007 11:36:22 AMAFAIL
Overspaced head at one location, final pending field ceiling tile install.
FIR06-00302 INSP-Alarm Testing5/8/20075/10/20075/10/2007 11:11:32 AMACANC
Inspection rescheduled as discussed.
FIR07-00295 INSP-Sprinkler Rough-in5/9/20075/10/20075/10/2007 11:04:03 AMAPART
Overhead fire sprinkler TI modifications are approved for ceiling cover, be aware of possible light fixture obstructions at some areas.
FIR07-00297 INSP-Sprinkler Rough-in5/9/20075/10/20075/10/2007 11:02:06 AMAPART
Rough-in is okay for cover at the hard lid ceilings.
FIR07-00356 INSP-Sprinkler Rough-in5/9/20075/10/20075/10/2007 11:00:58 AMAPART
OH FS install is good for cover at the hard lid ceiling areas.
FIR07-00299 INSP-Sprinkler Rough-in5/9/20075/10/20075/10/2007 10:59:41 AMAPART
OH is approved for cover, noted possible obstructions created by heads in close proximity to electrical junction boxes for light fixtures etc.
FIR07-00365 INSP-Sprinkler Rough-in5/9/20075/10/20075/10/2007 10:57:10 AMAFAIL
Mixed temp. heads in the same fire areas, some heads exceed allowable distance below the ceiling, several heads need to be replaced due to visible corrosion at the seat.
BLD06-02498 FIRE-Final Inspection5/9/20075/10/20075/10/2007 10:54:24 AMAPASS
Items on c/n verified for completion, life safety inspection passed.