FIR06-00886
| FIR-Aging Inspection | 5/10/2007 | 5/10/2007 | 5/16/2007 2:30:08 PM | | DONE |
|
|
Work in progress.
|
BLD06-02628
| FIRE-Final Inspection | 5/8/2007 | 5/10/2007 | 5/11/2007 3:40:20 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
BLD06-02256
| FIRE-Final Inspection | 5/8/2007 | 5/10/2007 | 5/11/2007 3:33:13 PM | A | PASS |
|
|
Fire life safety finaled.
|
BLD06-03343
| FIRE-Final Inspection | 5/9/2007 | 5/10/2007 | 5/11/2007 11:55:58 AM | A | PASS |
|
|
Corrections verified, fire life safety finaled.
|
FIR07-00072
| INSP-Alarm Testing | 5/8/2007 | 5/10/2007 | 5/11/2007 9:07:15 AM | P | PASS |
|
|
Fire alarm testing passed.
|
FIR07-00228
| INSP-Sprinkler Rough-in/Hydro | 5/8/2007 | 5/10/2007 | 5/11/2007 9:05:01 AM | A | PART |
|
|
OH rough-in and hydrostatic test both passed inspection.
|
BLD06-02628
| FIRE-Alarm Testing | 5/8/2007 | 5/10/2007 | 5/10/2007 4:44:05 PM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Rob Puckett
|
BLD06-02256
| FIRE-Alarm Testing | 5/8/2007 | 5/10/2007 | 5/10/2007 4:43:37 PM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Rob Puckett
|
FIR06-00689
| INSP-Final Inspection | 5/8/2007 | 5/10/2007 | 5/10/2007 4:42:04 PM | A | PASS |
|
|
Fire alarm permit finaled.
|
FIR06-00689
| INSP-Alarm Testing | 5/8/2007 | 5/10/2007 | 5/10/2007 4:41:26 PM | A | PASS |
|
|
Fire alarm work tested satisfactory.
|
FIR06-00595
| INSP-Alarm Testing | 5/9/2007 | 5/10/2007 | 5/10/2007 4:35:44 PM | A | CANC |
|
|
don; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
MIS07-00103
| FIR-Final | 5/10/2007 | 5/10/2007 | 5/10/2007 4:34:39 PM | P | PASS |
|
|
Life safety acceptable.
|
MIS07-00102
| FIR-Final | 5/10/2007 | 5/10/2007 | 5/10/2007 4:33:14 PM | P | PASS |
|
|
Life safety finaled.
|
MIS07-00101
| FIR-Final | 5/10/2007 | 5/10/2007 | 5/10/2007 4:32:06 PM | P | PASS |
|
|
Life safety passed inspection.
|
BLD07-00340
| FIRE-Final Inspection | 5/9/2007 | 5/10/2007 | 5/10/2007 4:31:00 PM | A | PASS |
|
|
Fire life safety passed.
|
FIR07-00120
| INSP-Final Inspection | 5/9/2007 | 5/10/2007 | 5/10/2007 4:30:02 PM | A | PASS |
|
|
Fire alarm syst. corrections complete, inspection passed, permit finaled.
|
FIR07-00192
| INSP-Final Inspection | 5/9/2007 | 5/10/2007 | 5/10/2007 4:28:16 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR07-00362
| INSP-Final Inspection | 5/9/2007 | 5/10/2007 | 5/10/2007 4:26:22 PM | P | PASS |
|
|
Fire sprinkler work passed inspection, permit finaled.
|
BLD06-02729
| FIRE-Final Inspection | 5/9/2007 | 5/10/2007 | 5/10/2007 12:39:19 PM | A | FAIL |
|
|
Provide one additional PFE for the kitchen area and mount the remaining fire extinguishers as discussed, remove manual thumbturn lock at the SE employee restroom, provide missing emergency lighting for the metro coffee shop, remove one exit sign as agreed.
|
FIR07-00240
| INSP-Final Inspection | 5/9/2007 | 5/10/2007 | 5/10/2007 11:37:57 AM | A | PASS |
|
|
Final FS permit inspection passed, corrections complete.
|
FIR07-00286
| INSP-Final Inspection | 5/8/2007 | 5/10/2007 | 5/10/2007 11:36:22 AM | A | FAIL |
|
|
Overspaced head at one location, final pending field ceiling tile install.
|
FIR06-00302
| INSP-Alarm Testing | 5/8/2007 | 5/10/2007 | 5/10/2007 11:11:32 AM | A | CANC |
|
|
Inspection rescheduled as discussed.
|
FIR07-00295
| INSP-Sprinkler Rough-in | 5/9/2007 | 5/10/2007 | 5/10/2007 11:04:03 AM | A | PART |
|
|
Overhead fire sprinkler TI modifications are approved for ceiling cover, be aware of possible light fixture obstructions at some areas.
|
FIR07-00297
| INSP-Sprinkler Rough-in | 5/9/2007 | 5/10/2007 | 5/10/2007 11:02:06 AM | A | PART |
|
|
Rough-in is okay for cover at the hard lid ceilings.
|
FIR07-00356
| INSP-Sprinkler Rough-in | 5/9/2007 | 5/10/2007 | 5/10/2007 11:00:58 AM | A | PART |
|
|
OH FS install is good for cover at the hard lid ceiling areas.
|
FIR07-00299
| INSP-Sprinkler Rough-in | 5/9/2007 | 5/10/2007 | 5/10/2007 10:59:41 AM | A | PART |
|
|
OH is approved for cover, noted possible obstructions created by heads in close proximity to electrical junction boxes for light fixtures etc.
|
FIR07-00365
| INSP-Sprinkler Rough-in | 5/9/2007 | 5/10/2007 | 5/10/2007 10:57:10 AM | A | FAIL |
|
|
Mixed temp. heads in the same fire areas, some heads exceed allowable distance below the ceiling, several heads need to be replaced due to visible corrosion at the seat.
|
BLD06-02498
| FIRE-Final Inspection | 5/9/2007 | 5/10/2007 | 5/10/2007 10:54:24 AM | A | PASS |
|
|
Items on c/n verified for completion, life safety inspection passed.
|