ELE10-00969
| Temporary Service | 5/10/2010 | 5/10/2010 | 5/10/2010 3:08:42 PM | P | PASS |
|
|
Inspection requested from web by: daniel bibikov Phone #: ###-####. T/S U/G Connect ok.
|
ELE10-00393
| Final | 5/10/2010 | 5/10/2010 | 5/10/2010 2:51:39 PM | P | PASS |
|
|
Please call for information on how to get in if not open. Thank you Inspection requested from web by: Rhonda Yoast Phone #: ###-####
|
ELE10-00393
| DOC - Permit Finaled | 5/10/2010 | 5/10/2010 | 5/10/2010 2:51:27 PM | P | PASS |
|
|
|
ELE10-00420
| Final | 5/8/2010 | 5/10/2010 | 5/10/2010 2:26:20 PM | P | PASS |
|
|
1/2 hr notice please Inspection requested from web by: Andy Derrick Phone #: ###-####
|
ELE10-00420
| DOC - Permit Finaled | 5/10/2010 | 5/10/2010 | 5/10/2010 2:26:12 PM | P | PASS |
|
|
|
ELE10-01010
| Permanent Service | 5/10/2010 | 5/10/2010 | 5/10/2010 2:26:01 PM | P | PASS |
|
|
Jay Phone #: ###-####. P/S O/H Connect ok.
|
ELE10-00968
| Permanent Service | 5/7/2010 | 5/10/2010 | 5/10/2010 2:25:03 PM | P | FAIL |
|
|
Final on New Service. Inspection requested from web by: Randy Fletcher Phone #: ###-####. NEC 334.80 #6 romex only rated at 55 amps. Need load calc for sub panel. NEC 250.8, 250.148 J box grounding.
|