Inspections for the day of: Thursday, May 10, 2012.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00184 INSP-Final Inspection5/10/20125/10/20125/11/2012 12:48:33 PMPPART
Overhead modifications at the remodel area okay for cover. As-built plans accepted. Final pending ceiling tile and escutcheons.
BLD11-00930 FIRE-Final Inspection5/10/20125/10/20125/11/2012 12:47:10 PMPPASS
Fire life safety inspection passed.
FIR11-00569 INSP-Final Inspection5/4/20125/10/20125/11/2012 12:46:26 PMPPASS
Fire alarm testing completed satisfactory. Permit final approved.
FIR11-00578 INSP-Supply line flush5/10/20125/10/20125/10/2012 3:51:41 PMPPART
UG fire supply line flush completed.
FIR12-00059 INSP-Sprinkler Rough-in/Hydro5/10/20125/10/20125/10/2012 3:50:42 PMPPART
Hydrostatic testing for the 2nd floor system completed satisfactory.
FIR11-00651 INSP-Sprinkler Rough-in5/10/20125/10/20125/10/2012 3:49:43 PMAPART
Regarding overhead wet system rough-in.
FIR12-00192 INSP-Sprinkler Rough-in/Hydro5/9/20125/10/20125/10/2012 3:47:58 PMAPART
C/N items include one overspaced head at bedroom 13, missing hangers on the 1 1/4" system tie in at bedroom 12, noted possible light fixture obstructions at bedrooms 8 and 9 due to proximity of pendent heads and LF J-boxes.
BLD11-00444 FIRE-Final Inspection5/10/20125/10/20125/10/2012 3:43:52 PMAPASS
Life safety final approved.
BLD12-00920 FIRE-Final Inspection5/10/20125/10/20125/10/2012 3:43:19 PMANR
FIR12-00192 INSP-Sprinkler Rough-in5/9/20125/10/20125/9/2012 11:35:06 AMPCANC
Phone #: ###-#### >> Inspection requested via web by John Venche Inspection cancelled from web by: John Venche