PLM16-01341
| Plumbing Rough-in | 5/9/2016 | 5/10/2016 | 5/10/2016 4:29:20 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ann Marie Reyes
|
PLM16-00532
| Final | 5/10/2016 | 5/10/2016 | 5/10/2016 3:45:31 PM | P | FAIL |
|
|
if questions call Chad @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann >608.5 ISPC—Relief valve drain piping shall not be smaller than the relief valve outlet, material used shall not reduce the internal bore of the pipe. Flex connector is not an approved material for T&P piping. >608.5 ISPC T&P shall not be trapped. >413.1 ISPC Hot water delivered from public use lavatories shall be limited to a maximum temperature of 120 degrees F by a device that conforms to ASSE 1070. > locate end of the line cleanout.
|
PLM16-01657
| Final | 5/10/2016 | 5/10/2016 | 5/10/2016 3:14:44 PM | P | PART |
|
|
3ish please call Eric ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss >not able to verify co detectors were installed. >wh ok
|
PLM16-01193
| Final | 5/10/2016 | 5/10/2016 | 5/10/2016 2:50:11 PM | P | NR |
|
|
Phone #: ###-#### Inspection requested via web by Branden Steers
|
PLM16-01649
| Groundwork | 5/9/2016 | 5/10/2016 | 5/10/2016 2:36:24 PM | P | PASS |
|
|
Home owner will be home after 2:00 pm, her cell # is ###-#### Phone #: ###-#### Inspection requested via web by bob pond >may need bld permit, h/o to check
|
PLM16-01648
| Plumbing Rough-in | 5/9/2016 | 5/10/2016 | 5/10/2016 2:14:32 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Travis Baker >Travis to add missing nail plate, ri ok.
|
PLM15-04344
| Plumbing Rough-in | 5/9/2016 | 5/10/2016 | 5/10/2016 1:48:54 PM | P | PART |
|
|
DON IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER >bathrooms ok to cover
|
PLM16-01676
| Sprinkler (Final) | 5/10/2016 | 5/10/2016 | 5/10/2016 1:24:34 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darrell Roark
|
PLM16-01677
| Water and/or Sewer | 5/10/2016 | 5/10/2016 | 5/10/2016 11:39:38 AM | P | PART |
|
|
Inspection requested via web by john brown >w/s stubs into bldg ok, sewer to be bored across parking lot later and new meter can to be set later.
|
PLM16-00109
| Final | 5/9/2016 | 5/10/2016 | 5/10/2016 11:15:06 AM | A | PASS |
|
|
if questions call Mark @ ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann
|
PLM16-01641
| DOC - Permit Finaled | 5/10/2016 | 5/10/2016 | 5/10/2016 10:56:50 AM | P | PASS |
|
|
|
PLM16-01641
| Plumbing Rough-in | 5/6/2016 | 5/10/2016 | 5/10/2016 10:56:24 AM | A | PASS |
|
|
This is a ReBath quick remodel and will need a rough-in and final inspection all at once. If you have any questions please call Andy at ###-####. Phone #: ###-#### Inspection requested via web by william bouck >RI and trim ok
|
PLM16-01673
| Plumbing Rough-in | 5/10/2016 | 5/10/2016 | 5/10/2016 10:11:11 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Branden Steers Inspection cancelled from web by: Branden Steers
|
PLM16-01643
| Final | 5/9/2016 | 5/10/2016 | 5/10/2016 9:55:22 AM | A | PASS |
|
|
Please call Jeb with any questions or concerns at ###-#### Phone #: ###-#### Inspection requested via web by Ben Davis
|
PLM16-01629
| Final | 5/5/2016 | 5/10/2016 | 5/10/2016 9:30:02 AM | A | PASS |
|
|
Please call Robert at ###-#### when en route Phone #: ###-#### Inspection requested via web by Erin Whiting
|
PLM16-01666
| Water Heater Final | 5/9/2016 | 5/10/2016 | 5/10/2016 9:11:00 AM | A | PASS |
|
|
Customer should be home Phone #: ###-#### Inspection requested via web by Ryan Baker
|
PLM16-01661
| DOC - Permit Finaled | 5/10/2016 | 5/10/2016 | 5/10/2016 8:52:08 AM | P | PASS |
|
|
|
PLM16-01661
| Final | 5/9/2016 | 5/10/2016 | 5/10/2016 8:51:56 AM | A | PASS |
|
|
Add gas line to stove Phone #: ###-#### Inspection requested via web by Nick Drake >Please read for next time. G2417.1.4 (406.1.4) IRC Under no circumstances shall a valve in a line be used as a bulkhead between gas in one section of the piping system and test medium in an adjacent section, unless two valves are installed in series with a valved "tell-tale” located between these valves.
|
PLM15-03461
| PLM-Aging Inspection | 5/10/2016 | 5/10/2016 | 5/10/2016 8:02:57 AM | | PART |
|
|
wip
|