Inspections for the day of: Tuesday, May 10, 2016.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00155 INSP-Conference5/9/20165/10/20165/10/2016 2:36:14 PMPCANC
Conference request will be rescheduled due to a doctors appointment per conversation with Richard, conference will be rescheduled for a later date.
FIR16-00281 INSP-Sprinkler Rough-in5/9/20165/10/20165/10/2016 2:33:25 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover. One fire sprinkler head was not installed at the receptionist area, will verify install at final inspection.
FIR16-00051 INSP-Final Inspection5/9/20165/10/20165/10/2016 1:45:45 PMPPASS
Final fire sprinkler inspection passed/complete. Activated irrigation timer, had water flowing from lawn sprinklers, opened inspectors test for water flow, after 27 seconds the exterior bell rang and the lawn irrigation shut off, providing all water flow to fire sprinkler inspectors test as notated on city approved drawings.
FIR16-00198 INSP-Final Inspection5/10/20165/10/20165/10/2016 1:42:11 PMPPASS
Final fire sprinkler inspection passed/complete.
FIR16-00206 INSP-Sprinkler Rough-in5/10/20165/10/20165/10/2016 10:40:44 AMPCANC
Duplicate inspection request, area of inspection requested has been approved for cover.
FIR16-00206 INSP-Sprinkler Rough-in5/9/20165/10/20165/10/2016 10:23:59 AMAPASS
Rough to cover inspection for north side corridor located in basement level complete, north side basement corridor approved for cover.
BLD15-01585 FIRE-Final Inspection5/9/20165/10/20165/10/2016 10:18:03 AMAFAIL
Small documentation was not attached to the city approved drawings, fire plan review small documentation needs to be with city approved drawings before next inspection. No knox box installed, knox box needs to ordered/installed before final inspection. No exit discharge emergency egress lighting installed at time of inspection, exit discharge emergency egress lighting will need to be installed before final inspection. Addressing needs to be installed on the exterior of building.
FIR16-00169 INSP-Final Inspection5/10/20165/10/20165/10/2016 8:11:39 AMPPASS
Final fire alarm inspection passed/complete
FIR13-00312 INSP-Final Inspection5/10/20165/10/20165/10/2016 8:03:50 AMAPASS
Final fire alarm inspection passed/complete.
FIR16-00028 INSP-Sprinkler Rough-in5/9/20165/10/20165/10/2016 6:14:11 AMAFAIL
No tenting on overhead fire sprinkler piping installed at time of inspection, inspection request will need to be scheduled when overhead fire sprinkler tenting is installed.
FIR16-00089 INSP-Sprinkler Rough-in/Hydro5/10/20165/10/20165/10/2016 5:44:08 AMAPART
Rough to cover inspection complete for level 4, level 4 approved for cover. 200 psi hydrostatic test complete for level 4.
FIR15-00602 INSP-Supply line flush5/4/20165/10/20165/10/2016 5:39:01 AMADONE
Underground supply flush complete, both supply mains have now been flushed.