FIR16-00155
| INSP-Conference | 5/9/2016 | 5/10/2016 | 5/10/2016 2:36:14 PM | P | CANC |
|
|
Conference request will be rescheduled due to a doctors appointment per conversation with Richard, conference will be rescheduled for a later date.
|
FIR16-00281
| INSP-Sprinkler Rough-in | 5/9/2016 | 5/10/2016 | 5/10/2016 2:33:25 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover. One fire sprinkler head was not installed at the receptionist area, will verify install at final inspection.
|
FIR16-00051
| INSP-Final Inspection | 5/9/2016 | 5/10/2016 | 5/10/2016 1:45:45 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete. Activated irrigation timer, had water flowing from lawn sprinklers, opened inspectors test for water flow, after 27 seconds the exterior bell rang and the lawn irrigation shut off, providing all water flow to fire sprinkler inspectors test as notated on city approved drawings.
|
FIR16-00198
| INSP-Final Inspection | 5/10/2016 | 5/10/2016 | 5/10/2016 1:42:11 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete.
|
FIR16-00206
| INSP-Sprinkler Rough-in | 5/10/2016 | 5/10/2016 | 5/10/2016 10:40:44 AM | P | CANC |
|
|
Duplicate inspection request, area of inspection requested has been approved for cover.
|
FIR16-00206
| INSP-Sprinkler Rough-in | 5/9/2016 | 5/10/2016 | 5/10/2016 10:23:59 AM | A | PASS |
|
|
Rough to cover inspection for north side corridor located in basement level complete, north side basement corridor approved for cover.
|
BLD15-01585
| FIRE-Final Inspection | 5/9/2016 | 5/10/2016 | 5/10/2016 10:18:03 AM | A | FAIL |
|
|
Small documentation was not attached to the city approved drawings, fire plan review small documentation needs to be with city approved drawings before next inspection. No knox box installed, knox box needs to ordered/installed before final inspection. No exit discharge emergency egress lighting installed at time of inspection, exit discharge emergency egress lighting will need to be installed before final inspection. Addressing needs to be installed on the exterior of building.
|
FIR16-00169
| INSP-Final Inspection | 5/10/2016 | 5/10/2016 | 5/10/2016 8:11:39 AM | P | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR13-00312
| INSP-Final Inspection | 5/10/2016 | 5/10/2016 | 5/10/2016 8:03:50 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete.
|
FIR16-00028
| INSP-Sprinkler Rough-in | 5/9/2016 | 5/10/2016 | 5/10/2016 6:14:11 AM | A | FAIL |
|
|
No tenting on overhead fire sprinkler piping installed at time of inspection, inspection request will need to be scheduled when overhead fire sprinkler tenting is installed.
|
FIR16-00089
| INSP-Sprinkler Rough-in/Hydro | 5/10/2016 | 5/10/2016 | 5/10/2016 5:44:08 AM | A | PART |
|
|
Rough to cover inspection complete for level 4, level 4 approved for cover. 200 psi hydrostatic test complete for level 4.
|
FIR15-00602
| INSP-Supply line flush | 5/4/2016 | 5/10/2016 | 5/10/2016 5:39:01 AM | A | DONE |
|
|
Underground supply flush complete, both supply mains have now been flushed.
|