Inspections for the day of: Wednesday, May 10, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03931 Electrical Rough-In5/9/20175/10/20175/10/2017 4:26:02 PMPPASS
ceiling rough-in 3rd floor corridors 335B, 335A, 336A. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Different floor 635 A and B, 636 A firelid rough in ok cover. Discussed peninsula area for kitchen counters receptacles. One additional on wall where peninsula attched.
ELE16-00580 Electrical Rough-In5/9/20175/10/20175/10/2017 4:14:19 PMPPASS
rough-in walls in mezzanine M06 Phone #: ###-#### Inspection requested via web by Cathy Duchek Wall rough in ok cover
ELE17-01320 Permanent Service5/9/20175/10/20175/10/2017 4:08:50 PMPFAIL
Phone #: ###-#### Inspection requested via web by JENNY EMEL
110.24- Available fault current shall be posted prior to permenant service inspection to verify main disconnect rated for current available at line terminals as per 110.9. 10k rated main breakers.
10,959 L-L...8,217 L-N. Next size shall be installed.
ELE17-00116 Electrical Rough-In5/10/20175/10/20175/10/2017 3:02:18 PMPFAIL
Ceiling Rough-In Inspection
Contact Jon Novak
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
110.12(A)- Unused openings shall be closed by approved means. KO seals
300.15- Found fixture whip... needs terminated in a box or removed.
314.25- Open junction boxes...cover or remove.
330.30- MC if supported by support wires, support wire shall be secured at both ends.
ELE16-04167 Final5/9/20175/10/20175/10/2017 2:46:27 PMAFAIL
Justin Hamby Phone #: ###-#### Inspection requested via web by Laurie Hoelscher
600.3- Unable to verify listing.
600.6- Unable to verify disconnecting means
ELE16-03864 Extend Permit 180 days5/10/20175/10/20175/10/2017 12:25:40 PMPPASS
Due to scheduling issues owner own job has fallen behind needs extra time to complete. Extension OK
ELE17-00578 Electrical Rough-In5/9/20175/10/20175/10/2017 11:12:02 AMAPASS
Phone #: ###-#### Inspection requested via web by Mark M
Grid rough in ok cover
ELE17-00396 Final5/9/20175/10/20175/10/2017 10:21:05 AMAFAIL
Lock box on front tree. Code is 2017 Phone #: ###-#### Inspection requested via web by Barbara Szurgot
BCC 4-05-32 Code violations not to be retained.
400.12- Flexible cords shall not pass thru walls. Utility to front planter left of front door. Remove cord.
406.12- All 120 volt receptacle outlets install in a dwelling shall be tamper resistant type. Master vanity between basins
ELE17-00430 Final5/9/20175/10/20175/10/2017 9:43:49 AMAFAIL
Garage code is 3303 Phone #: ###-#### Inspection requested via web by TOM BICANDI
110.3- Raise disposal receptacle to accept air switch.
210.8- All 120 volt receptacle outlets serving kitchen counter top areas shall have GFCI protection.
ELE17-00372 Final5/9/20175/10/20175/10/2017 9:42:18 AMAFAIL
Garage code is 3303 Phone #: ###-#### Inspection requested via web by TOM BICANDI
110.3- Family room lighting not working and switched power at stack switch for nook lighting.
210.8- All receptacle outlets serving kitchen counter top areas shall have GFCI protection. Pantry