ELE16-03931
| Electrical Rough-In | 5/9/2017 | 5/10/2017 | 5/10/2017 4:26:02 PM | P | PASS |
|
|
ceiling rough-in 3rd floor corridors 335B, 335A, 336A. Phone #: ###-#### Inspection requested via web by Cathy Duchek Different floor 635 A and B, 636 A firelid rough in ok cover. Discussed peninsula area for kitchen counters receptacles. One additional on wall where peninsula attched.
|
ELE16-00580
| Electrical Rough-In | 5/9/2017 | 5/10/2017 | 5/10/2017 4:14:19 PM | P | PASS |
|
|
rough-in walls in mezzanine M06 Phone #: ###-#### Inspection requested via web by Cathy Duchek Wall rough in ok cover
|
ELE17-01320
| Permanent Service | 5/9/2017 | 5/10/2017 | 5/10/2017 4:08:50 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by JENNY EMEL 110.24- Available fault current shall be posted prior to permenant service inspection to verify main disconnect rated for current available at line terminals as per 110.9. 10k rated main breakers. 10,959 L-L...8,217 L-N. Next size shall be installed.
|
ELE17-00116
| Electrical Rough-In | 5/10/2017 | 5/10/2017 | 5/10/2017 3:02:18 PM | P | FAIL |
|
|
Ceiling Rough-In Inspection Contact Jon Novak Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 110.12(A)- Unused openings shall be closed by approved means. KO seals 300.15- Found fixture whip... needs terminated in a box or removed. 314.25- Open junction boxes...cover or remove. 330.30- MC if supported by support wires, support wire shall be secured at both ends.
|
ELE16-04167
| Final | 5/9/2017 | 5/10/2017 | 5/10/2017 2:46:27 PM | A | FAIL |
|
|
Justin Hamby Phone #: ###-#### Inspection requested via web by Laurie Hoelscher 600.3- Unable to verify listing. 600.6- Unable to verify disconnecting means
|
ELE16-03864
| Extend Permit 180 days | 5/10/2017 | 5/10/2017 | 5/10/2017 12:25:40 PM | P | PASS |
|
|
Due to scheduling issues owner own job has fallen behind needs extra time to complete. Extension OK
|
ELE17-00578
| Electrical Rough-In | 5/9/2017 | 5/10/2017 | 5/10/2017 11:12:02 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mark M Grid rough in ok cover
|
ELE17-00396
| Final | 5/9/2017 | 5/10/2017 | 5/10/2017 10:21:05 AM | A | FAIL |
|
|
Lock box on front tree. Code is 2017 Phone #: ###-#### Inspection requested via web by Barbara Szurgot BCC 4-05-32 Code violations not to be retained. 400.12- Flexible cords shall not pass thru walls. Utility to front planter left of front door. Remove cord. 406.12- All 120 volt receptacle outlets install in a dwelling shall be tamper resistant type. Master vanity between basins
|
ELE17-00430
| Final | 5/9/2017 | 5/10/2017 | 5/10/2017 9:43:49 AM | A | FAIL |
|
|
Garage code is 3303 Phone #: ###-#### Inspection requested via web by TOM BICANDI 110.3- Raise disposal receptacle to accept air switch. 210.8- All 120 volt receptacle outlets serving kitchen counter top areas shall have GFCI protection.
|
ELE17-00372
| Final | 5/9/2017 | 5/10/2017 | 5/10/2017 9:42:18 AM | A | FAIL |
|
|
Garage code is 3303 Phone #: ###-#### Inspection requested via web by TOM BICANDI 110.3- Family room lighting not working and switched power at stack switch for nook lighting. 210.8- All receptacle outlets serving kitchen counter top areas shall have GFCI protection. Pantry
|