FIR16-00267
| INSP-Sprinkler Rough-in | 5/10/2017 | 5/10/2017 | 5/10/2017 4:20:00 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping located above hardlids on east wing complete, levels 3, 4, 5 and 6, all hardlids on noted levels for east wing approved for cover.
|
BLD17-01058
| FIRE-Final Inspection | 5/10/2017 | 5/10/2017 | 5/10/2017 3:02:49 PM | P | FAIL |
|
|
Exit sign located above south exit needs to be serviced, hood suppression system needs to be serviced/inspected and tagged before final life fire safety inspection, class K fire extinguisher needs to be inspected/serviced and a current inspection tag placed, fire extinguisher with a current inspection tag needs to be installed in seating area, existing grill tops that will be used for seating need to be disconnected from energy source (gas and or electrical power), surface mount slide bolt locks on northeast interior door needs to be removed, padlock clasp on interior office door needs to be removed, signage for exterior gate needs to be installed reading "Gate to remain unlocked while occupied" per approved drawings note, fire sprinkler head next to northwest door needs to be replaced due to excessive external loading, missing escutcheons need to be installed on fire sprinkler heads.
|
BLD16-03359
| FIRE-Final Inspection | 5/10/2017 | 5/10/2017 | 5/10/2017 2:00:57 PM | P | CANC |
|
|
Project has rooms that have modifications to the fire alarm system (FIR17-00189, permit is not attached in project related cases), audio visual device modifications need to be tested, inspected and passed before final inspection for life fire safety can be completed. This inspection request is cancelled and will be rescheduled by contractor to coincide with fire alarm final.
|
FIR17-00151
| INSP-Sprinkler Rough-in | 5/9/2017 | 5/10/2017 | 5/10/2017 12:05:10 PM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in area of work complete, approved for cover.
|
FIR17-00152
| INSP-Sprinkler Rough-in | 5/9/2017 | 5/10/2017 | 5/10/2017 12:04:30 PM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in area of work complete, approved for cover.
|
BLD17-00293
| FIRE-Conference | 5/10/2017 | 5/10/2017 | 5/10/2017 11:52:01 AM | P | DONE |
|
|
Fire conference complete, fire extinguisher will be mounted in discussed location.
|
FIR16-00755
| INSP-Sprinkler Rough-in | 5/10/2017 | 5/10/2017 | 5/10/2017 10:55:54 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
|
FIR16-00742
| INSP-Sprinkler Rough-in/Hydro | 5/9/2017 | 5/10/2017 | 5/10/2017 10:18:50 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR16-00743
| INSP-Sprinkler Rough-in/Hydro | 5/9/2017 | 5/10/2017 | 5/10/2017 10:18:36 AM | A | CANC |
|
|
Inspection requested via web by Sam Ball
|
FIR16-00770
| INSP-Sprinkler Rough-in | 5/9/2017 | 5/10/2017 | 5/9/2017 3:35:43 PM | A | PASS |
|
|
Rough to cover inspection for underground completed on 1/26/2017
|