FIR19-00105
| INSP-Final Inspection | 5/9/2019 | 5/10/2019 | 5/10/2019 12:28:55 PM | A | PASS |
|
|
Tested sprinkler monitor, passed fire alarm test.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
FIR19-00164
| INSP-Final Inspection | 5/9/2019 | 5/10/2019 | 5/10/2019 12:28:14 PM | A | PASS |
|
|
Fire alarm testing on sprinkler monitor complete. Need as build for troubles on tamper as panel unable to do supervisory signal.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
FIR19-00098
| INSP-Final Inspection | 5/10/2019 | 5/10/2019 | 5/10/2019 12:27:09 PM | A | PASS |
|
|
Passed fire alarm testing. State Fire to send in as build showing trouble instead of supervisory on tampers as panel has no supervisory function.
Doug Phone #: ###-####
|
BLD18-00494
| FIRE-Final Inspection | 5/8/2019 | 5/10/2019 | 5/10/2019 11:03:11 AM | P | PASS |
|
|
Passed fire life safety.n e-lights, exit lights and extinguishers all checked.
Scott Phone #: ###-####
|
FIR18-00690
| INSP-Final Inspection | 5/9/2019 | 5/10/2019 | 5/10/2019 11:02:23 AM | A | PART |
|
|
Tested system. TCO of 10 days granted to verify 6 corrections. Approved by Ron Johnson
ada room strobes do not turn off until reset. sounders in rooms 101, 107, 118 sound steady (bad base).
2 smokes in beam pockets to be lowered to bottom of beam (greater than .1 less than .4)
Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
FIR18-00673
| INSP-Final Inspection | 5/9/2019 | 5/10/2019 | 5/10/2019 10:49:15 AM | A | PASS |
|
|
Corrections have been made. Eschuchons, heads fixed and signs placed. Passed
Todd Phone #: ###-####
|