Inspections for the day of: Tuesday, May 11, 2004.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-00695 FIRE-Final Inspection5/10/20045/11/20045/11/2004 12:00:00 AMANR
Dave; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
BLD03-02579 FIRE-Final Inspection5/11/20045/11/20045/11/2004 12:00:00 AMPFAIL
Mount fire extinguishers at 48". Provide approved door hardware on all doors. Lever type is ok. See building dept. review note #12. Provide sticker over main exit per review note #9. Provide occupant load sign per review note #11. Remove all dead bolts on the exterior doors. Provide type one hood and suppression system or variance. 5/11/2004 3:42:08 PM