Inspections for the day of: Wednesday, May 11, 2005.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-01980 FIRE-Final Inspection5/11/20055/11/20055/11/2005 4:14:28 PMPFAIL
Contact Ron Hill with the building dept. about wall modifications. With walls as installed , sprinkler coverage at the rear door is blocked. Remove steel bar blocking/locking the rear exit door. Repair or remove the emergency light in the sales area. Repa
FIR05-00248 INSP-Sprinkler Rough-in5/11/20055/11/20055/11/2005 4:03:12 PMPPART
Inspection was for underground cover. Piping matches resubmitted plans and is ok to cover.
FIR05-00149 INSP-Sprinkler Rough-in/Hydro5/11/20055/11/20055/11/2005 3:59:59 PMPPART
Sprinkler rough-in and above ground hydro passed. Still need to inspect pipe to verify insulation is properly placed before sheet rock is installed.
FIR04-00664 INSP-Supply line flush5/11/20055/11/20055/11/2005 2:23:15 PMPPASS
Inspection was for an underground hydro which passed
MIS05-00041 FIR-Final5/11/20055/11/20055/11/2005 12:13:17 PMPPASS
Fire life safety finaled
BLD05-00043 FIRE-Final Inspection5/10/20055/11/20055/11/2005 8:40:23 AMAPASS
fire life safety finaled
BLD04-02113 FIRE-Final Inspection5/10/20055/11/20055/11/2005 8:39:57 AMAPASS
fire life safety finaled
BLD05-00113 FIRE-Final Inspection5/11/20055/11/20055/11/2005 12:00:00 AMPPASS
Fire life safety finaled