ELE07-01387
| Final | 5/11/2007 | 5/11/2007 | 5/11/2007 3:07:28 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ok card signed
|
ELE07-01706
| Permanent Service | 5/11/2007 | 5/11/2007 | 5/11/2007 2:38:50 PM | P | FAIL |
|
|
ron ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see added r/i corr called 250.119&550.33 ID equip grd green both ends, 312.5 needs conn for GEC, 250.56 needs 2 grd rods
|
ELE07-01706
| Electrical Rough-In | 5/11/2007 | 5/11/2007 | 5/11/2007 2:37:14 PM | P | PASS |
|
|
ron ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith trench ok
|
ELE07-01715
| Electrical Rough-In | 5/11/2007 | 5/11/2007 | 5/11/2007 2:10:25 PM | P | PASS |
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE06-04572
| Permanent Service | 5/10/2007 | 5/11/2007 | 5/11/2007 1:47:11 PM | P | FAIL |
|
|
doug; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr. called 110.3(B) use GE breakers only subpanel, 250.104(A)(1)& 220.64(E) shall remove GEC from subpanel and raceway , and terminate it at p/s
|
ELE07-01576
| Rough-In Permanent Service | 5/11/2007 | 5/11/2007 | 5/11/2007 1:09:52 PM | P | FAIL |
|
|
contact jeff ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson corr called left message all 4 units, 314.3 no steel fittings in plastic boxes (range), 314.20 all outside boxes shall be flush, 314.17 staple 8" of boxes, 250.24 terminate GEC at neutral bus not equip grd bus, BCC complete all makeup and have attic accesses installed
|
ELE06-01085
| DOC - Permit Expired | 5/11/2007 | 5/11/2007 | 5/11/2007 10:32:09 AM | A | PASS |
|
|
no response back from the last time I called
|
ELE06-00711
| Electrical Rough-In | 5/10/2007 | 5/11/2007 | 5/11/2007 9:59:10 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 5/10/2007 at 11:43:25 AM. Contact: ###-####. 3rd floor 2 rms west bowtie, 2nd floor north tower NE corner anop
|
ELE07-00494
| Permanent Service | 5/10/2007 | 5/11/2007 | 5/11/2007 8:33:01 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot p/s u/g new ok
|