Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01387 Final5/11/20075/11/20075/11/2007 3:07:28 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ok card signed
ELE07-01706 Permanent Service5/11/20075/11/20075/11/2007 2:38:50 PMPFAIL
ron ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see added r/i
corr called 250.119&550.33 ID equip grd green both ends, 312.5 needs conn for GEC, 250.56 needs 2 grd rods
ELE07-01706 Electrical Rough-In5/11/20075/11/20075/11/2007 2:37:14 PMPPASS
ron ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith trench ok
ELE07-01715 Electrical Rough-In5/11/20075/11/20075/11/2007 2:10:25 PMPPASS
lloyd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE06-04572 Permanent Service5/10/20075/11/20075/11/2007 1:47:11 PMPFAIL
doug; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
corr. called 110.3(B) use GE breakers only subpanel, 250.104(A)(1)& 220.64(E) shall remove GEC from subpanel and raceway , and terminate it at p/s
ELE07-01576 Rough-In Permanent Service5/11/20075/11/20075/11/2007 1:09:52 PMPFAIL
contact jeff ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson corr called left message all 4 units, 314.3 no steel fittings in plastic boxes (range), 314.20 all outside boxes shall be flush, 314.17 staple 8" of boxes, 250.24 terminate GEC at neutral bus not equip grd bus, BCC complete all makeup and have attic accesses installed
ELE06-01085 DOC - Permit Expired5/11/20075/11/20075/11/2007 10:32:09 AMAPASS
no response back from the last time I called
ELE06-00711 Electrical Rough-In5/10/20075/11/20075/11/2007 9:59:10 AMAPART
Scheduled by a contractor via Hello! on 5/10/2007 at 11:43:25 AM. Contact: ###-####. 3rd floor 2 rms west bowtie, 2nd floor north tower NE corner anop
ELE07-00494 Permanent Service5/10/20075/11/20075/11/2007 8:33:01 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
p/s u/g new ok