Inspections for the day of: Friday, May 11, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01719 Electrical Rough-In5/11/20075/11/20075/11/2007 3:32:04 PMPPASS
u/g ok to cover from house to garage only
ELE07-01634 Electrical Rough-In5/11/20075/11/20075/11/2007 3:30:22 PMPPASS
under ground conduit Phone #: ###-#### Internet Inspection Request from: Brandon Blackham u/g ok to cover house to garage
ELE07-01465 Electrical Rough-In5/10/20075/11/20075/11/2007 3:23:08 PMAFAIL
Underground & Pool Grid bonding inspection. Please call Steve Ruter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson called, left corr notice, nec 680.26(B) news breif, rebar shall have minimum 12" squares and be tied at each cross, called contr to verify split bolt listed for rebar and for being poured in concrete
ELE07-01423 Electrical Rough-In5/11/20075/11/20075/11/2007 2:57:48 PMPPASS
under ground conduit Phone #: ###-#### Internet Inspection Request from: Brandon Blackham u/g ok to cover house to garage
ELE07-01384 Electrical Rough-In5/11/20075/11/20075/11/2007 2:26:31 PMPPASS
underground conduit Phone #: ###-#### Internet Inspection Request from: Brandon Blackham u/g house to garage ok to cover
ELE07-01307 Electrical Rough-In5/11/20075/11/20075/11/2007 1:59:30 PMPPASS
under ground conduit Phone #: ###-#### Internet Inspection Request from: Brandon Blackham u/g house to garage ok to cover
ELE07-01108 Electrical Rough-In5/11/20075/11/20075/11/2007 1:29:28 PMPPASS
under ground conduit Phone #: ###-#### Internet Inspection Request from: Brandon Blackham u/g house to garage ok to cover
ELE07-01087 Conference5/10/20075/11/20075/11/2007 12:47:48 PMPDONE
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall met owner, looked at service, changing from o/h to u/g. New service was put on about 3 years ago, so owner mainly needs to just switch gec over to new service an split up branch circuits.
ELE07-01624 Electrical Rough-In5/11/20075/11/20075/11/2007 10:43:26 AMPPASS
Carl ###-#### concrete encased gec ok to pour, ground ring continuous in all footing
ELE07-01692 Permanent Service5/11/20075/11/20075/11/2007 10:09:43 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Jim Williams p/s, exst meter base, n, ok
ELE07-01690 Electrical Rough-In5/10/20075/11/20075/11/2007 9:08:59 AMAFAIL
Mike; Phone #: ###-#### Internet Inspection Request from: Darla Downs called, left corr notice nec 300.4(A) & (D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members
ELE07-00834 Electrical Rough-In5/10/20075/11/20075/11/2007 7:58:11 AMAFAIL
trench inspection in planter beds Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called, left corr notice, nec 300.5 raceways shall be minimum 18" from top of raceway to finished surface