FIR06-00719
| INSP-Final Inspection | 5/11/2007 | 5/11/2007 | 5/11/2007 4:43:25 PM | P | PASS |
|
|
permit finaled
|
FIR05-00536
| INSP-Sprinkler Rough-in | 5/10/2007 | 5/11/2007 | 5/11/2007 3:56:22 PM | A | PASS |
|
|
The remaining hardlids on the eigth floor are ok to cover. Also the piping under the first floor stairs is ok to cover
|
FIR06-00958
| INSP-Sprinkler Rough-in | 5/10/2007 | 5/11/2007 | 5/11/2007 3:54:20 PM | A | PASS |
|
|
Area A attic system is ok to cover.
|
FIR07-00375
| INSP-Final Inspection | 5/10/2007 | 5/11/2007 | 5/11/2007 1:57:45 PM | A | PASS |
|
|
permit finaled
|
FIR07-00130
| INSP-Sprinkler Rough-in | 5/10/2007 | 5/11/2007 | 5/11/2007 12:25:05 PM | A | FAIL |
|
|
There are many errors including unattached hangers and inadequate tenting. Pipe sizing does not match the plans. The piping in the central first floor area does not match the plans, a loop has been installed. The anti-freeze loop shows two heads but four are actually installed and this is a remote area. Also the anti-freeze loop piping is smaller than what is shown. The revise attic piping plan was not available for inspection of the attic piping.
|
FIR06-00536
| INSP-Final Inspection | 5/9/2007 | 5/11/2007 | 5/11/2007 10:57:26 AM | A | FAIL |
|
|
The fire pump acceptance test passed. Fire sprinkler rough-in passed. Contractor supplied certification that the fire pump package had been hydro tested. The backflow was certified as I waited. To final the project the signage on the riser room door needs to be installed and the orfice to test the flow switch needs to be provided. The ventilation and drainage as is will be acceptable. Emergency lighting has been provided.
|
FIR07-00103
| FIR-Aging Inspection | 5/11/2007 | 5/11/2007 | 5/11/2007 9:04:48 AM | | NR |
|
|
Work is in progress
|
FIR07-00130
| INSP-Sprinkler Rough-in | 5/10/2007 | 5/11/2007 | 5/10/2007 5:02:31 PM | A | CANC |
|
|
Please call Brian prior to inspection. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|