Inspections for the day of: Friday, May 11, 2007.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00719 INSP-Final Inspection5/11/20075/11/20075/11/2007 4:43:25 PMPPASS
permit finaled
FIR05-00536 INSP-Sprinkler Rough-in5/10/20075/11/20075/11/2007 3:56:22 PMAPASS
The remaining hardlids on the eigth floor are ok to cover. Also the piping under the first floor stairs is ok to cover
FIR06-00958 INSP-Sprinkler Rough-in5/10/20075/11/20075/11/2007 3:54:20 PMAPASS
Area A attic system is ok to cover.
FIR07-00375 INSP-Final Inspection5/10/20075/11/20075/11/2007 1:57:45 PMAPASS
permit finaled
FIR07-00130 INSP-Sprinkler Rough-in5/10/20075/11/20075/11/2007 12:25:05 PMAFAIL
There are many errors including unattached hangers and inadequate tenting. Pipe sizing does not match the plans. The piping in the central first floor area does not match the plans, a loop has been installed. The anti-freeze loop shows two heads but four are actually installed and this is a remote area. Also the anti-freeze loop piping is smaller than what is shown. The revise attic piping plan was not available for inspection of the attic piping.
FIR06-00536 INSP-Final Inspection5/9/20075/11/20075/11/2007 10:57:26 AMAFAIL
The fire pump acceptance test passed. Fire sprinkler rough-in passed. Contractor supplied certification that the fire pump package had been hydro tested. The backflow was certified as I waited. To final the project the signage on the riser room door needs to be installed and the orfice to test the flow switch needs to be provided. The ventilation and drainage as is will be acceptable. Emergency lighting has been provided.
FIR07-00103 FIR-Aging Inspection5/11/20075/11/20075/11/2007 9:04:48 AM NR
Work is in progress
FIR07-00130 INSP-Sprinkler Rough-in5/10/20075/11/20075/10/2007 5:02:31 PMACANC
Please call Brian prior to inspection. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus