ESC12-00147
| General Inspection | 5/10/2012 | 5/10/2012 | | | |
|
|
|
ELE11-00099
| ELE-Aging Inspection | 5/11/2012 | 5/11/2012 | 5/17/2012 7:45:36 AM | | DONE |
|
|
|
ELE11-00169
| ELE-Aging Inspection | 5/11/2012 | 5/11/2012 | 5/17/2012 7:44:07 AM | | PASS |
|
|
wsuc
|
ELE12-00987
| Electrical Rough-In | 5/11/2012 | 5/11/2012 | 5/11/2012 2:51:55 PM | P | PASS |
|
|
ron Phone #: ###-####ceiling and walls
|
ELE12-00830
| Final | 5/11/2012 | 5/11/2012 | 5/11/2012 2:51:25 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Chris Berthelot
|
ELE12-01064
| Temporary Service | 5/10/2012 | 5/11/2012 | 5/11/2012 1:57:12 PM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Quinten Bair called correction posted 300.10&12 tighten all locknuts, secure both recetacle enclosures to the pole 314.23 200.6 shall not ID 6 or smaller, shall use white or gray neutral to 230V recept
|
ELE12-00937
| Final | 5/10/2012 | 5/11/2012 | 5/11/2012 1:50:34 PM | A | PASS |
|
|
Access - There is a key stashed at the base of the pillar to the left of the front door. It is a single key on a key-chain. You can call if you need more information. Contact is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery ok card signed
|
GCE12-00064
| GCE-Permanent Service | 5/11/2012 | 5/11/2012 | 5/11/2012 1:03:05 PM | P | PASS |
|
|
Tom @ ###-#### called, shall provide a GEC tap,per NEC art 250.64(D)(1) p/s u/g new ok for meter
|
ELE12-01062
| Permanent Service | 5/10/2012 | 5/11/2012 | 5/11/2012 11:49:03 AM | A | FAIL |
|
|
Brent Phone #: ###-#### called correction posted 250.53 needs 6ft between grd rods, secure j bos under trailer314.23, 250.122T needs #6 to grd j box under trailer
|
ELE12-01061
| Permanent Service | 5/10/2012 | 5/11/2012 | 5/11/2012 11:45:40 AM | A | FAIL |
|
|
Need Inspectiom for Idaho Power to reconnect power as it has been off for more than 1 year. Phone #: ###-#### >> Inspection requested via web by Cindie Swaim called needs to check out meter and label breaker with address
|
ELE12-00424
| Final | 5/8/2012 | 5/11/2012 | 5/11/2012 11:43:06 AM | A | FAIL |
|
|
Swimming pool electrical final. Access backyard through gate on left side of residence. Phone #: ###-#### >> Inspection requested via web by Lars Johnson called bonding of cover rails and pump not done
|
ELE12-01055
| Electrical Rough-In | 5/11/2012 | 5/11/2012 | 5/11/2012 11:39:56 AM | A | PASS |
|
|
corrections have been made Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman ok both units
|
ELE12-00802
| Conference | 5/10/2012 | 5/11/2012 | 5/11/2012 9:28:12 AM | A | DONE |
|
|
conference with Greg and Luke on fir pump and new power for it
|