BLD15-01260
| FIRE-Final Inspection | 5/11/2015 | 5/11/2015 | 5/11/2015 3:31:05 PM | P | FAIL |
|
|
Provide fire extinguisher and exit sign/emergency light at the west exit door per the city approved plans.
|
NAF15-00016
| INSP-Final | 5/11/2015 | 5/11/2015 | 5/11/2015 2:57:28 PM | P | CANC |
|
|
Per contractor the hood suppression system/electrical shunt is not wired correctly. No inspection was performed.
|
BLD13-00317
| FIRE-Conference | 5/11/2015 | 5/11/2015 | 5/11/2015 2:55:29 PM | P | DONE |
|
|
No city approved plans on site but I performed a conference anyway. I noted that the main building address is not visible from Ustick Rd, missing tagged fire extinguishes on lower and upper levels and that many of the smoke alarms are installed less than 3'-0" from bathrooms containing a tub or shower.
|
FIR13-00612
| INSP-Final Inspection | 5/8/2015 | 5/11/2015 | 5/11/2015 2:46:55 PM | P | PASS |
|
|
Permit finaled. FDC relocated, with fire dept approval, to the north side parking lot access.
|
FIR14-00435
| INSP-Final Inspection | 5/8/2015 | 5/11/2015 | 5/11/2015 2:45:44 PM | P | PASS |
|
|
permit finaled
|
BLD15-01527
| FIRE-Final Inspection | 5/8/2015 | 5/11/2015 | 5/11/2015 1:37:15 PM | A | FAIL |
|
|
Provide single action hardware, remove thumbturn dead bolt and provide sticker at the main exit.
|
FIR15-00054
| INSP-Final Inspection | 5/11/2015 | 5/11/2015 | 5/11/2015 12:56:33 PM | P | PASS |
|
|
Permit finaled
|
BLD15-00417
| FIRE-Final Inspection | 5/8/2015 | 5/11/2015 | 5/11/2015 12:31:47 PM | A | CANC |
|
|
Need the project related fire alarm permit to be issued/inspected prior to a life safety inspection
|
BLD15-01464
| FIRE-Final Inspection | 5/8/2015 | 5/11/2015 | 5/11/2015 12:24:48 PM | A | FAIL |
|
|
One pendant head in the conference room is overspaced. This work will require a permit. All other life safety items ok.
|
BLD15-01277
| FIRE-Final Inspection | 5/11/2015 | 5/11/2015 | 5/11/2015 9:10:15 AM | P | PASS |
|
|
life safety passed
|
BLD14-03511
| FIRE-Final Inspection | 5/8/2015 | 5/11/2015 | 5/11/2015 8:58:37 AM | A | PASS |
|
|
life safety passed
|
BLD15-01277
| FIRE-Final Inspection | 5/8/2015 | 5/11/2015 | 5/11/2015 8:23:54 AM | A | FAIL |
|
|
Provide fire extinguisher as discussed and the sticker at the main exit door.
|
FIR05-00238
| FIR-Aging Inspection | 5/11/2015 | 5/11/2015 | 5/11/2015 7:07:14 AM | | NR |
|
|
I spoke to Dave and he is going to follow up.
|