Inspections for the day of: Wednesday, May 11, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-04318 FIRE-Final Inspection5/11/20165/11/20165/11/2016 2:55:32 PMPPASS
No fire sprinklers, commercial hood suppression system inspection complete (FIR16-00148), fire alarm inspection complete (FIR16-00144) , fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00144 INSP-Final Inspection5/10/20165/11/20165/11/2016 2:53:26 PMPPASS
Final fire alarm inspection passed/complete.
FIR16-00148 INSP-Final Inspection5/9/20165/11/20165/11/2016 2:51:21 PMPPASS
Final commercial hood fire suppression system inspection passed/complete.
FIR16-00290 INSP-Sprinkler Rough-in5/11/20165/11/20165/11/2016 12:42:21 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping located above hardlids complete, fire sprinkler piping above hardlids approved for cover.
FIR16-00278 INSP-Sprinkler Rough-in5/10/20165/11/20165/11/2016 12:38:04 PMPPASS
Rough to cover inspection for fire sprinkler piping above suspended ceilings complete, overhead fire sprinkler piping located above suspended ceilings approved for cover.
FIR16-00028 INSP-Sprinkler Rough-in5/10/20165/11/20165/11/2016 12:35:46 PMAPART
Tenting inspection for level 4 complete, overhead fire sprinkler approved for cover on level 4 with exception to the fire sprinkler piping crossing the breezeway, this piping cannot be covered (as well as levels 1,2 and 3) until an acceptable means of keeping the pipe from freezing is inspected and passed.. Tenting for sprinkler piping in attic space on level 3 still not installed, overhead fire sprinkler piping in attic space on level 3 not approved for cover.
BLD16-00127 FIRE-Conference5/11/20165/11/20165/11/2016 10:39:04 AMPDONE
Fire conference complete
FIR16-00038 INSP-Final Inspection5/10/20165/11/20165/11/2016 10:02:02 AMPPASS
Final fire sprinkler nspection passed/complete
FIR15-00602 INSP-Sprinkler Rough-in/Hydro5/10/20165/11/20165/11/2016 9:37:04 AMAPASS
Northwest underground supply hydrostatic test complete, this completes underground hydrostatic tests.
FIR15-00767 INSP-Final Inspection5/10/20165/11/20165/11/2016 9:13:45 AMAPART
Project is being worked in phases, contractor is going floor by floor for partial inspection and a final alarm inspection for entire building at project completion. Inspected level 3 smoke detectors and pull stations, remaining detection on level 3 is VESDA systems which will be tested at a later date. Level 1 smoke detectors/duct detectors/pull stations spot checked, devices tested operated correctly. Level 1 inspection complete, partial completion for level 3, contractor will schedule inspection request when other area's are ready.
BLD16-00762 FIRE-Final Inspection5/10/20165/11/20165/11/2016 12:00:00 AMPCANC
Joey Phone #: ###-####