Inspections for the day of: Thursday, May 11, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-01946 Electrical Rough-In5/11/20175/11/20175/11/2017 1:58:48 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Mezz grid rough in ok cover
ELE16-04045 Final5/11/20175/11/20175/11/2017 1:21:54 PMPFAIL
Phone #: ###-#### Inspection requested via web by Greg Idsinga
110.3- Receptacle in up bed by window shows open ground, correct or GFCI protect as per 406.4(D).
110.14- Unused openings shall be closed. 2 breaker blanks in panel.
300.4- 10-3 NM cable shall be protected from physical damage where it enters panel/meter combo.
408.41- Grounded conductors shall terminate in an individual terminal.
ELE17-01320 Permanent Service5/11/20175/11/20175/11/2017 11:28:41 AMPPASS
Re-Inspection of service panel moved from one location to another Phone #: ###-#### Inspection requested via web by JENNY EMEL
Main breaker B changed to 22k rating others to be changed Monday the15th as they are on order.
p/s u/g n ok
ELE17-00676 Electrical Rough-In5/10/20175/11/20175/11/2017 11:08:25 AMAPASS
Inspect temp trailer and breezeway. Phone #: ###-#### Inspection requested via web by Tom Jenkins
Temp trailer for bank teller wall receptacles added rough in ok cover
ELE16-03897 Final5/10/20175/11/20175/11/2017 10:25:44 AMANR
unit will be unlocked Phone #: ###-#### Inspection requested via web by Robert Schroder
Called in by mistake
ELE16-03574 Final5/10/20175/11/20175/11/2017 10:25:12 AMAPASS
unit will be unlocked Phone #: ###-#### Inspection requested via web by Robert Schroder Final ok
ELE16-03573 Final5/10/20175/11/20175/11/2017 10:24:48 AMAPASS
unit will be unlocked Phone #: ###-#### Inspection requested via web by Robert Schroder Final ok
ELE17-00116 Electrical Rough-In5/11/20175/11/20175/11/2017 9:39:43 AMAPASS
Ceiling Inspection
Contact Jon Novak
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Grid rough in as noted on contractor print rough in ok cover
ELE17-00372 Final5/10/20175/11/20175/11/2017 8:31:18 AMAPASS
Garage code is 3033 Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
ELE17-00430 Final5/10/20175/11/20175/11/2017 8:30:56 AMAPASS
Garage code is 3033 Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok