Inspections for the day of: Monday, May 12, 2003.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-00521 ELE-Aging Inspection5/12/20035/12/20035/12/2003 12:00:00 AM PART
WSUC 5/12/2003 12:48:42 PM
ELE02-03810 Final5/7/20035/12/20035/12/2003 12:00:00 AMAFAIL
TONY; Phone #: ###-#### Internet Inspection Request from: Annette Moore this is a p/s not final conference only needs grds , clearenece for mast asnt service pane see JF 5/12/2003 9:35:39 AM
ELE03-00923 Electrical Rough-In5/9/20035/12/20035/12/2003 12:00:00 AMANH
###-#### notice posted called left message 5/12/2003 12:06:45 PM
ELE03-01375 Electrical Rough-In5/9/20035/12/20035/12/2003 12:00:00 AMAFAIL
###-#### Larry called needs 11/4 , and support for MC cable 5/12/2003 11:16:09 AM
ELE03-01378 Final5/9/20035/12/20035/12/2003 12:00:00 AMAFAIL
jim ###-#### ; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called 110.26(F)(2) move gas pipe or sub panel for required clearence 5/12/2003 10:18:15 AM
ELE03-01338 Electrical Rough-In5/8/20035/12/20035/12/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 5/8/2003 at 11:27:11 AM. Contact: ###-####. r/i ok survey posted 314.16 5/12/2003 4:16:52 PM
ELE03-01380 Rough-In Permanent Service5/12/20035/12/20035/12/2003 12:00:00 AMPPASS
###-#### darrell r/i ok

p/s o/h new ok 5/12/2003 4:45:01 PM
ELE03-01348 Final5/12/20035/12/20035/12/2003 12:00:00 AMPFAIL
chris; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called 110.3(B) use manufactures listed bus when used as service equip, 404.6 (C) line and load ,250.24(A) tie neutral and grd together at p/s 5/12/2003 1:55:16 PM
ELE02-01916 ELE-Request for Extension5/12/20035/12/20035/12/2003 12:00:00 AMPPART
###-#### andy talked with owner extension ok 5/12/2003 3:12:07 PM
ELE02-03810 Permanent Service5/12/20035/12/20035/12/2003 12:00:00 AMPPASS
tony; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
p/s o/h rec. ok 5/12/2003 3:47:52 PM