Inspections for the day of: Monday, May 12, 2003.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-00251 FIRE-Final Inspection5/8/20035/12/20035/12/2003 12:00:00 AMAFAIL
###-#### Paint curbing for the fire lane per review note #3 and drawing G101. Provide "Door to remain unlocked during business hours" at the main entry/exit. Remove manual flush bosts from the main entry/exit. See IFC 1003.3.1.8.1. Remove thumbturn from the west door. Provide one additinal emergency light at the west door in the corridor. Test other emergency light in the same corridor. 5/12/2003 8:59:24 AM
FIR03-00175 INSP-Sprinkler Rough-in/Hydro5/11/20035/12/20035/12/2003 12:00:00 AMPFAIL
Hangers and sway bracing have been corrected but no insulation has been added yet. Per the contractor the insulation will be completed tomorrow and an inspection called in. 5/12/2003 4:00:19 PM
FIR02-00316 INSP-Final Inspection5/12/20035/12/20035/12/2003 12:00:00 AMPPASS
Retest the hood for light and recepticle shutdown. Provide panel keys for knox box. Provide map for facp. Provide room numbers on map. Lounge 130 pull station is mis labeled. Verify signals with fax 5/12/2003 3:23:41 PM
BLD03-00483 FIRE-Final Inspection5/12/20035/12/20035/12/2003 12:00:00 AMPFAIL
Duct smoke detector came in at the fire alarm panel but did not shutdown the hvac unit or activate the remote alarm led 5/12/2003 3:25:23 PM
FIR03-00223 INSP-Final Inspection5/12/20035/12/20035/12/2003 12:00:00 AMPPASS
FIR02-00423 INSP-Final Inspection5/12/20035/12/20035/12/2003 12:00:00 AMPPASS