BLD03-02994
| FIRE-Final Inspection | 5/12/2004 | 5/12/2004 | 5/13/2004 12:00:00 AM | A | PASS |
|
|
air balance report okay 5/13/2004 10:54:35 AM
|
FIR02-00005
| INSP-Sprinkler Rough-in | 5/11/2004 | 5/12/2004 | 5/12/2004 12:00:00 AM | A | FAIL |
|
|
Brian; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Need EQ on 4 inch on either side of skylight as they are overspaced 5/12/2004 11:26:04 AM
|
MIS04-00127
| FIR-Final | 5/11/2004 | 5/12/2004 | 5/12/2004 12:00:00 AM | A | PASS |
|
|
Hal; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
FIR03-00807
| INSP-Alarm Testing | 5/12/2004 | 5/12/2004 | 5/12/2004 12:00:00 AM | P | PASS |
|
|
Cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
|
FIR03-00708
| INSP-Alarm Testing | 5/12/2004 | 5/12/2004 | 5/12/2004 12:00:00 AM | P | PASS |
|
|
Cell Ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
|
FIR04-00153
| INSP-Alarm Testing | 5/12/2004 | 5/12/2004 | 5/12/2004 12:00:00 AM | P | FAIL |
|
|
earl; Phone #: ###-#### Internet Inspection Request from: Barbara Moore tampers for sprinkler controls reversed addresses; need to test flow switches, pull stations; remove all old devices 5/13/2004 7:28:11 AM
|
FIR04-00125
| INSP-Alarm Testing | 5/12/2004 | 5/12/2004 | 5/12/2004 12:00:00 AM | P | FAIL |
|
|
earl; Phone #: ###-#### Internet Inspection Request from: Barbara Moore old NAC devices not working and devices on 7th floor not working; candela on strobes not per plans; zone 4 on 6th floor not working; verify all candelas; test flows and all new devices 5/13/2004 7:29:44 AM
|
FIR04-00118
| INSP-Final Inspection | 5/12/2004 | 5/12/2004 | 5/12/2004 12:00:00 AM | P | FAIL |
|
|
Two sprinkler heads were not replaced to make clearance for RF units on second floor 5/12/2004 3:24:45 PM
|
FIR03-00784
| INSP-Final Inspection | 5/12/2004 | 5/12/2004 | 5/12/2004 12:00:00 AM | P | PASS |
|
|
|