FIR05-00212
| INSP-Final Inspection | 5/12/2005 | 5/12/2005 | 5/12/2005 3:21:46 PM | P | CANC |
|
|
Wrong permit number called in, not ready for this inspection. Actual inspection done was for cleanroom in fab (addition of 3 heads).
|
BLD05-00224
| FIRE-Final Inspection | 5/11/2005 | 5/12/2005 | 5/12/2005 12:36:48 PM | A | FAIL |
|
|
Sign off pending resolution of fire sprinkler issue. All other life safety items OK.
|
FIR05-00065
| INSP-Final Inspection | 5/11/2005 | 5/12/2005 | 5/12/2005 12:33:56 PM | A | FAIL |
|
|
Provide calcs. to prove two heads off 1" pipe, or verify rated room separation area.
|
FIR05-00079
| INSP-Final Inspection | 5/11/2005 | 5/12/2005 | 5/12/2005 12:30:51 PM | A | PASS |
|
|
Fire alarm finaled.
|
BLD05-00692
| FIRE-Final Inspection | 5/11/2005 | 5/12/2005 | 5/12/2005 9:36:55 AM | A | PASS |
|
|
Fire life safety finaled.
|
FIR05-00225
| INSP-Final Inspection | 5/11/2005 | 5/12/2005 | 5/12/2005 9:35:37 AM | A | FAIL |
|
|
Need hanger installed within 2' of the end at arm over in confrence room west side. Pendent in office is too close to heat diffuser, general contractor said he would move diffuser.
|
FIR05-00200
| INSP-Final Inspection | 5/12/2005 | 5/12/2005 | 5/12/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler finaled.
|
BLD05-00424
| FIRE-Final Inspection | 5/12/2005 | 5/12/2005 | 5/12/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled.
|
BLD04-03026
| FIRE-Conference | 5/12/2005 | 5/12/2005 | 5/12/2005 12:00:00 AM | P | DONE |
|
|
Site visited to check status of building permit work. Some correction notice items not yet complete such as mount provided fire ext. Discovered tenant has moved in and is open for business without sign off or CO. Informed Sam Rogers of the situation.
|