Inspections for the day of: Thursday, May 12, 2005.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-01882 FIRE-Conference5/11/20055/12/20055/12/2005 4:24:29 PMPFAIL
bill ; Phone #: ###-#### Could not make contact either on the phone or at the project site.
FIR05-00009 INSP-Final Inspection5/12/20055/12/20055/12/2005 1:35:21 PMPPASS
Fire sprinkler finaled
FIR04-00531 INSP-Sprinkler Rough-in5/10/20055/12/20055/12/2005 12:49:45 PMAPART
The sprinkler piping for the exterior canopies is ok to cover. There is wood in areas above the ceiling in these exterior canopies. I notified the sprinkler contractor and the general contractor that this would have to be addressed since there are no upri
FIR05-00109 INSP-Final Inspection5/11/20055/12/20055/12/2005 12:46:26 PMAFAIL
The zone #1 smoke detectors located in the storage room are not connected to the fire alarm system. Provide knox key box per review comments. Provide faxed verification of the signals.
BLD00-02716 FIRE-Final Inspection5/10/20055/12/20055/12/2005 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 5/10/2005 at 3:34:54 PM. Contact: ###-####.\\No fire inspection to be done(SFD home)