ELE06-01683
| Rough-In Permanent Service | 5/12/2006 | 5/12/2006 | 5/12/2006 4:14:15 PM | P | PASS |
|
|
John; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt grd rods ok for now will call for concrete encased electrode when ready p/s u/g new ok
|
ELE06-01414
| Final | 5/12/2006 | 5/12/2006 | 5/12/2006 3:13:43 PM | P | FAIL |
|
|
craig; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. corr. not made 210.52(A) shall install outlet for wall space, 210.12 shall provide afci for all circuits in bed rm
|
ELE06-01690
| Temporary Service | 5/12/2006 | 5/12/2006 | 5/12/2006 2:43:59 PM | P | PASS |
|
|
Chris; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt t/s o/h new ok
|
ELE06-01110
| Electrical Rough-In | 5/12/2006 | 5/12/2006 | 5/12/2006 1:37:22 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/12/2006 at 7:13:37 AM. Contact: ###-####. grid ceilings and front desk stub wall ok
|
ELE05-04600
| Permanent Service | 5/12/2006 | 5/12/2006 | 5/12/2006 1:36:43 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/12/2006 at 7:11:34 AM. Contact: ###-####. p/s u/g new ok
|
ELE06-01463
| Final | 5/11/2006 | 5/12/2006 | 5/12/2006 11:56:58 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/11/2006 at 3:16:19 PM. Contact: ###-####. no access early in the am stopped back later final ok card signed
|
ELE06-00444
| Final | 5/12/2006 | 5/12/2006 | 5/12/2006 10:42:06 AM | A | PASS |
|
|
per jack frank send this insp ok
|
ELE05-03660
| Electrical Rough-In | 5/11/2006 | 5/12/2006 | 5/12/2006 9:46:12 AM | A | PART |
|
|
rough in for storage room Internet Inspection Request from: Andy Rose ok walls
|
ELE06-01673
| Electrical Rough-In | 5/11/2006 | 5/12/2006 | 5/12/2006 9:14:30 AM | A | PART |
|
|
need inspection on conduit to hot tub so it can be burried. Call Andy @ ###-#### if have any qustions Internet Inspection Request from: Andy Rose u/g ok
|
ELE06-01236
| Electrical Rough-In | 5/11/2006 | 5/12/2006 | 5/12/2006 8:38:53 AM | A | PASS |
|
|
please inspect the concrete on the ufer ground so I can flip the power; Phone #: ###-#### Internet Inspection Request from: steve creswell ok
|
ELE06-01236
| Permanent Service | 5/12/2006 | 5/12/2006 | 5/12/2006 8:38:37 AM | A | PASS |
|
|
please inspect the concrete on the ufer ground so I can flip the power; Phone #: ###-#### Internet Inspection Request from: steve creswell p/s o/h new ok
|
ELE06-01659
| Temporary Service | 5/11/2006 | 5/12/2006 | 5/12/2006 8:03:44 AM | A | PASS |
|
|
Re-inspection; Phone #: ###-#### Internet Inspection Request from: Dan Surerus t/s u/g new ok
|