Inspections for the day of: Friday, May 12, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01609 Permanent Service5/12/20065/12/20065/12/2006 4:13:08 PMPPASS
paul ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
P/S U/G R Ok
ELE06-00271 Temporary Service5/12/20065/12/20065/12/2006 3:25:46 PMPNH
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
I could not locate this pole and the contractor didnot know anything about it.
ELE06-01450 Final5/12/20065/12/20065/12/2006 3:05:31 PMPNR
rhonda ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
scott; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover ceiling, wires for boxe must meet code or sheet rock to be removed to rewire lites and garage door outlet. Lt on above gar.dr. in alley on require pan box. 9/10/2004 1:22:48 PM This job has been finished with only this partial R/I Inspection. This is the only inspection record that I could find. I recommend a conf. on this job to gather more info and determine the action to be taken.
ELE05-04582 Final5/12/20065/12/20065/12/2006 2:05:19 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Danette Brookshirece passed with a survey for lock-out for furnace.
ELE05-04581 Final5/12/20065/12/20065/12/2006 2:04:11 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Danette Brookshire
provide lock-out for furnace.
missing recep in dinning room and small appliance circuit not working by refer
ELE05-04207 Final5/11/20065/12/20065/12/2006 11:38:54 AMANR
Final inspection for 05/12 a.m. Contact is Greg @ ###-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Steve Syltie
stil no listing label on pump
ELE06-01382 Rough-In Permanent Service5/11/20065/12/20065/12/2006 10:37:21 AMAPASS
todd lanham; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
R/I Ok
P/S O/H N Ok
ELE06-00511 Electrical Rough-In5/11/20065/12/20065/12/2006 10:15:38 AMANR
This is for a rough-in in the reception area. Any questions please give Chris Hill a call.; Phone #: ###-#### Internet Inspection Request from: Jeff Radford
had a conf. about suport and protection of mc and flex.
ELE06-00134 Final5/12/20065/12/20065/12/2006 9:55:30 AMAFAIL
Dave Hanna approved energy code for lighting changes. new certificate on-site. ; Phone #: ###-#### Internet Inspection Request from: Kevin Braithwait
406.4 Receptacle Mounting.
(C) Receptacles Mounted on Covers. Front reception area.

110.3 Examination, Identification, Installation, and Use of Equipment.
400.8 Uses Not Permitted.
410.14 Connection of Electric-Discharge Luminaires (Lighting Fixtures).
Down stairs fixtures
314.27 Outlet Boxes.
Upstairs hallway fixtures
The lighting outlet boxes upstairs will be exposed on final because the cut-in boxes are being changed in the area where the ceiling was dropped.
ELE06-01105 Final5/11/20065/12/20065/12/2006 8:55:28 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Latisha Peltier
no card
ELE06-01373 Electrical Rough-In5/11/20065/12/20065/12/2006 8:24:08 AMAPASS
jeff Note: please 1/2 hr; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
R/I Ok
ELE05-03544 Final5/11/20065/12/20065/12/2006 12:00:00 AMPCANC
richard ; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cancell by richard
ELE06-01450 Final5/12/20065/12/20065/12/2006 12:00:00 AMPCANC
rhonda; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--cancel not ready yet