FIR05-00397
| FIR-Aging Inspection | 5/12/2006 | 5/12/2006 | 5/17/2006 1:52:06 PM | | DONE |
|
|
Related project site permits are not complete at this time, wip.
|
FIR04-00313
| INSP-Final Inspection | 5/10/2006 | 5/12/2006 | 5/12/2006 3:22:38 PM | P | FAIL |
|
|
Electrical power under hood failed to shut down upon suppression system activation, also need to relocate the manual pull station to meet code requirements.
|
MIS06-00108
| FIR-Final | 5/12/2006 | 5/12/2006 | 5/12/2006 3:00:39 PM | P | PASS |
|
|
Corrections have been made, fire life safety passed final inspection.
|
FIR05-00513
| INSP-Final Inspection | 5/10/2006 | 5/12/2006 | 5/12/2006 2:02:37 PM | A | PASS |
|
|
Final fire sprinkler inspection is acceptable, permit finaled.
|
FIR06-00296
| INSP-Final Inspection | 5/10/2006 | 5/12/2006 | 5/12/2006 10:45:59 AM | A | PART |
|
|
Corrections for the overhead rough-in have been completed, installation is good for cover, final pending cooler construction for dry pendents and ceiling tile/escutcheons at the drop ceiling areas.
|
BLD05-03341
| FIRE-Final Inspection | 5/10/2006 | 5/12/2006 | 5/12/2006 12:00:00 AM | A | CANC |
|
|