Inspections for the day of: Monday, May 12, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00045 INSP-Sprinkler Rough-in5/12/20085/12/20085/12/2008 5:14:03 PMPNR
jerry Phone #: ###-####
FIR07-00818 INSP-Sprinkler Rough-in/Hydro5/12/20085/12/20085/12/2008 5:11:49 PMPPART
UG fire supply hydrostatic test is satisfactory.
FIR07-00606 INSP-Sprinkler Rough-in5/12/20085/12/20085/12/2008 5:11:06 PMPFAIL
OH rough-in inspection completed for areas G and H, see re-lined annotations on plan set for marked defficiencies including bracing, hangers, seismic clearance, spacing, obstructions at various locations, noted added head at the top of the SE elevator hoistway does not appear required and is not indicated on plans, tops of stairways and three skylights in the library are not yet installed, four head guards are missing at the gym.
FIR08-00286 INSP-Sprinkler Rough-in5/9/20085/12/20085/12/2008 3:08:13 PMAPART
OH fire sprinkler system modifications are approved for cover at the grid ceiling areas within the scope of permit work.
BLD07-02423 FIRE-Final Inspection5/11/20085/12/20085/12/2008 1:59:38 PMAPASS
Noted corrections have been completed, minor adjustments to duct sample tube orientation done while on site, fire life safety finaled.
FIR07-00606 INSP-Sprinkler Rough-in/Hydro5/9/20085/12/20085/12/2008 1:25:54 PMAPART
OH hydrostatic testing for system #3 only (gym system) passed.
FIR08-00101 INSP-Final Inspection5/12/20085/12/20085/12/2008 1:23:48 PMAPASS
Fire alarm field testing passed, horn strobe at the sub-fab cabinet to be re-attatched at discussed, permit finaled.
BLD08-00244 FIRE-Final Inspection5/12/20085/12/20085/12/2008 11:25:54 AMAPASS
Missing unit numbers and door closures to be installed prior to structural final for verification of compliance at that time as discussed, remainder of life safety okayed.