Inspections for the day of: Tuesday, May 12, 2009.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC09-00133 General Inspection5/12/20095/12/20095/12/2009 3:43:30 PMPPASS
ok
ELE09-00734 Final5/12/20095/12/20095/12/2009 3:42:57 PMPPASS
Please contact Bryan Atkins at ###-#### prior to inspection so that he can meet you onsite. Phone #: ###-#### Internet Inspection Request from: Bryan Atkins
ELE09-00734 Electrical Rough-In5/12/20095/12/20095/12/2009 3:42:49 PMPPASS
Please contact Bryan Atkins at ###-#### prior to inspection so that he can meet you onsite. Phone #: ###-#### Internet Inspection Request from: Bryan Atkins
needs to check for metallic raceways in plastic boxes
ELE09-00813 Electrical Rough-In5/12/20095/12/20095/12/2009 3:41:42 PMPFAIL
Steve- Call for access Phone #: ###-####
corr met contr, 314.3 metallic fittings in plastic boxes, 314.20 outside boxes shall be flush with siding at time of r/i, 250.148 splice all equip grds together at boxes, 300.14 free length, and use approved tool for crimp sleeves, BCC and 200.6 shall not ID 6or smaller neutral to pool
ELE09-00786 Final5/11/20095/12/20095/12/2009 2:17:30 PMPCANC
this will be a final inspection for new meter can and service mast install. Contact will be Mark Hood. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw contr. will reschedule when ready for p/s eequest
ELE09-00594 Final5/11/20095/12/20095/12/2009 1:55:06 PMPCANC
Ready for inspection. Electrician: Vince ###-#### Phone #: ###-#### Internet Inspection Request from: Clint Tate called needs ele attached to bld
ELE09-00807 Final5/11/20095/12/20095/12/2009 1:06:07 PMPPASS
Phone #: ###-#### Internet Inspection Request from: David Nelson
ELE09-00807 Electrical Rough-In5/12/20095/12/20095/12/2009 1:05:40 PMPPASS
Phone #: ###-#### Internet Inspection Request from: David Nelson
ELE09-00805 Permanent Service5/11/20095/12/20095/12/2009 12:17:52 PMPPASS
Andy Phone #: ###-#### called needs clearence for subpanel p/s u/g rec. ok
ELE09-00797 Conference5/8/20095/12/20095/12/2009 11:34:00 AMADONE
Vicki Phone #: ###-#### ok
ESC09-00215 Site Preparation5/12/20095/12/20095/12/2009 10:52:07 AMANR
talked with R P about cleanup and drain protection, he address items noted
ELE09-00795 Electrical Rough-In5/11/20095/12/20095/12/2009 10:50:23 AMAPART
bonding grid inspection//###-#### Mike ok
ELE07-03457 Electrical Rough-In5/11/20095/12/20095/12/2009 10:22:44 AMAPASS
joe Phone #: ###-#### u/g for new N E parking lot lights ok
ESC09-00107 General Inspection5/12/20095/12/20095/12/2009 9:37:12 AMAPASS
ok
ELE09-00666 Final5/11/20095/12/20095/12/2009 9:35:19 AMAFAIL
zack Phone #: ###-#### called needs floor box listed covers for floor outlets
ESC08-00490 General Inspection5/12/20095/12/20095/12/2009 9:09:32 AMAPART
clean up of hard surfaces in progress at time of inspection
ELE08-02208 Conference5/12/20095/12/20095/12/2009 9:07:23 AMADONE
Jason Phone #: ###-####-wall talked with contr. about ID of different voltages, phases and neutral, grding of separately derived systems
ELE07-03286 ELE-Aging Inspection5/12/20095/12/20095/12/2009 7:44:38 AM PART
wsuc
ELE07-03492 ELE-Aging Inspection5/12/20095/12/20095/12/2009 7:43:12 AM DONE
ELE07-03492 DOC - Permit Expired5/12/20095/12/20095/12/2009 7:42:16 AMAPASS
ELE09-00805 Final5/11/20095/12/20095/12/2009 12:00:00 AMPCANC
final on meter main replacement, will be ready in afternoon. Any questions call George @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose
ELE09-00778 Final5/11/20095/12/20095/11/2009 9:35:21 AMPCANC
This is for a final inspection for this job. Contact is Mark Hood. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw Inspection cancelled from web by: Laura Longshaw