FIR11-00184
| INSP-Final Inspection | 5/12/2011 | 5/12/2011 | 5/12/2011 5:07:23 PM | P | FAIL |
|
|
SD at two rooms need relocated, three manual pull stations are above 48" to the operable part. HD tested okay, remainder of smoke detectors not tested at this time.
|
BLD11-00964
| FIRE-Final Inspection | 5/12/2011 | 5/12/2011 | 5/12/2011 5:05:01 PM | P | FAIL |
|
|
Need to post fire extinguishers with current tags throughout, door hardware at several locations does not meet min. code requirements, exit signs and EM lights need repair.
|
BLD06-02323
| FIRE-Conference | 5/10/2011 | 5/12/2011 | 5/12/2011 5:02:09 PM | P | DONE |
|
|
On site conference with contractor and structural inspector regarding exiting at the pool enclosure.
|
FIR11-00175
| INSP-Sprinkler Rough-in/Hydro | 5/12/2011 | 5/12/2011 | 5/12/2011 4:59:32 PM | P | PART |
|
|
Overhead work okayed as noted on plans with the exception of four heads at cloud ceilings and one pendent at the grid ceiling not yet installed.
|
BLD11-00447
| FIRE-Final Inspection | 5/12/2011 | 5/12/2011 | 5/12/2011 4:58:07 PM | P | PASS |
|
|
Fire life safety okayed for final pending max. occupant load sign is posted and the fire extinguishers are attatched to the wall as discussed.
|
BLD11-00554
| FIRE-Final Inspection | 5/11/2011 | 5/12/2011 | 5/12/2011 4:57:41 PM | A | PASS |
|
|
Life safety passed re-inspection, correction items finished.
|
FIR11-00162
| INSP-Final Inspection | 5/11/2011 | 5/12/2011 | 5/12/2011 4:52:58 PM | A | PASS |
|
|
Fire alarm permit work passed inspection.
|