Inspections for the day of: Thursday, May 12, 2011.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00202 INSP-Final Inspection5/12/20115/12/20115/12/2011 4:14:14 PMPCANC
cancelled due to time constraints rescheduled for tomorrow morning.
BLD11-00354 FIRE-Conference5/12/20115/12/20115/12/2011 4:09:55 PMPDONE
Smoke evac system operated correctly. Waited on site while correct tenant address was entered into FACP.
BLD11-00805 FIRE-Final Inspection5/11/20115/12/20115/12/2011 10:29:52 AMAFAIL
Resubmit plans showing the all of the actual space being used. Repair the marked exit signs and emergency lights. Provide exit discharge ligthing at the exterior exits. Provide permits for storage racks over 8'-0" (racks now exceed 8') or storage over 12'-0" (no storage over 12' yet).
FIR11-00154 INSP-Sprinkler Rough-in5/11/20115/12/20115/12/2011 9:27:47 AMAPASS
Sprinkler piping is ok to cover.
FIR11-00154 INSP-Final Inspection5/11/20115/12/20115/12/2011 9:27:27 AMAFAIL
Can not final until the ceiling tile is installed.
FIR10-00647 INSP-Final Inspection5/11/20115/12/20115/12/2011 9:26:53 AMAPASS
Permit finaled