Inspections for the day of: Monday, May 12, 2014.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02164 ELE-Aging Inspection5/12/20145/12/20145/12/2014 3:18:20 PM DONE
Contractor to schedule
ELE08-02423 ELE-Aging Inspection5/12/20145/12/20145/12/2014 3:17:19 PM DONE
Still under construction
ELE13-03005 Final5/7/20145/12/20145/12/2014 3:11:15 PMPNH
Need a final for the job. Call Jimmy @ ###-#### for questions. Phone #: ###-#### >> Inspection requested via web by John Edwards No answer at door. Will reschedule
ELE14-00632 Electrical Rough-In5/12/20145/12/20145/12/2014 2:59:53 PMPPASS
Dave. Uffer ground. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Ufer for 2 electrical rooms located on south east corner of garages. underground for loops at entance and exit rough in ok cover.
ELE14-01188 Permanent Service5/12/20145/12/20145/12/2014 1:54:09 PMPPASS
Arron Phone #: ###-#### p/s o/h rec ok
ELE14-00883 Final5/12/20145/12/20145/12/2014 1:16:06 PMPPASS
Ben Phone #: ###-#### Final ok
ELE14-01155 Final5/12/20145/12/20145/12/2014 12:47:50 PMPPASS
Brent Phone #: ###-#### Service only Final ok
ELE14-01155 Permanent Service5/12/20145/12/20145/12/2014 12:31:19 PMPPASS
Brent Phone #: ###-#### p/s o/h rec ok
MIS14-00103 ELE-Conference5/12/20145/12/20145/12/2014 11:36:47 AMPDONE
BCC 4-05 17- Unlawful Electrical Procedures. (A)- It shall be unlawful to install or alter electrical wiring or equiptment without first securing electrical permit. 5 working days to secure permit.
ELE14-01194 Rough-In Permanent Service5/12/20145/12/20145/12/2014 10:37:38 AMAPASS
Remodel Phone #: ###-#### >> Inspection requested via web by TOM BICANDI rough in ok cover p/s o/h rec ok
ELE14-00952 Final5/9/20145/12/20145/12/2014 9:48:48 AMAFAIL
Wes (son to Rosalie) Phone #: ###-#### 250.53(D)- Underground metal pipe shall be supplemented by an additional groudning electrode.
250.53(C)- Grounding electrode bonding jumper shall be sized based on service entrance conductors, #4 minimum.
240.24(A)- Overcurrent devices shall be located so that handle of sircuit breakers do not exceed 6'7".
230.24(A)- Where overhead service mast is over 3' above roof it shall have additional support.
ELE14-01061 Permanent Service5/9/20145/12/20145/12/2014 9:06:36 AMAPASS
Contact is Greg Fuller. NOTE!! After inspector made the inspection yesterday afternoon for this same type of inspection, the service was change out to a dual 100A service pedestal. Phone #: ###-#### >> Inspection requested via web by Scott Campbell 2 meters p/s u/g n ok
GCE14-00064 GCE-Final5/9/20145/12/20145/12/2014 8:48:46 AMAPASS
JEFF ###-#### housewares department Drop to plug mold on top of shelf. Final ok