Inspections for the day of: Tuesday, May 12, 2015.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-01378 Final5/12/20155/12/20155/13/2015 9:10:08 AMPPASS
Please call prior. Not On site. Phone #: ###-#### Inspection requested via web by Garrett Collins No inspection on permit. Permit opened for a conference only. Discussed remodel and use of building. 200 amp service most likely not enough for body repair shop, service calc needed once building use is decided. Numerous penatrations in hazardous areas if used for auto repair garage. GFCI protection, doors for closets and offices need changed for hazard separation.
ELE14-02747 Final5/11/20155/12/20155/12/2015 3:41:41 PMPPART
MIke Phone #: ###-#### Oil lube bays ok temp occupancy
ELE15-00131 Electrical Rough-In5/12/20155/12/20155/12/2015 3:30:49 PMPFAIL
Carwash HVAC control 300.6(D)- Conduit system shall maintain 1/4" from wall for drainage
ELE15-01112 Final5/12/20155/12/20155/12/2015 3:06:50 PMPPASS
Phone #: ###-#### Inspection requested via web by Jessica Powell Final ok
ELE15-00867 Final5/12/20155/12/20155/12/2015 2:30:17 PMPPASS
Inspection requested via web by Rowdy Monroe Final ok
ELE15-01362 Electrical Rough-In5/12/20155/12/20155/12/2015 1:59:00 PMPPASS
underground; Mark Phone #: ###-#### Underground between buildings on north side and 1 run on wouth side of last building. rough in ok cover
ELE15-01141 Electrical Rough-In5/12/20155/12/20155/12/2015 1:05:36 PMPPASS
Ceiling cover Phone #: ###-#### Inspection requested via web by Karl Paige Dining room grid rough in ok cover
ELE15-00514 Final5/12/20155/12/20155/12/2015 10:57:49 AMPPASS
Ken Phone #: ###-#### UL listing and disconnecting means confirmed. Final ok
ELE15-00741 Final5/12/20155/12/20155/12/2015 10:53:19 AMPPASS
Phone #: ###-#### Inspection requested via web by Dan Rohl Final ok
ELE15-01350 Final5/11/20155/12/20155/12/2015 10:14:06 AMAPASS
Von. Phone #: ###-#### Inspection requested via web by Sean DeLacy Final ok
ELE15-01374 Final5/11/20155/12/20155/12/2015 9:54:13 AMANH
Building Inspector requested electrical inspection. for occupancy Phone #: ###-#### Inspection requested via web by Celinda Winters South east corner of building. Door locked. No access and no call back from John at ###-#### who did work, Jeff at numbe given not sure what was done.
ELE15-00926 Final5/11/20155/12/20155/12/2015 9:30:11 AMAPASS
Phone #: ###-#### Inspection requested via web by Bryan McLaughlin Final ok
ELE15-00601 Electrical Rough-In5/11/20155/12/20155/12/2015 9:00:49 AMAPASS
wall rough in please Phone #: ###-#### Inspection requested via web by Celinda Winters Enter thru back door. Offices off main storage area. Wall rough in ok cover
ELE15-00672 Final5/11/20155/12/20155/12/2015 8:38:38 AMAPASS
James is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Final ok
ELE11-02123 ELE-Aging Inspection5/12/20155/12/20155/12/2015 5:57:42 AM DONE
Still under construction