BLD15-00080
| FIRE-Final Inspection | 5/11/2015 | 5/12/2015 | 5/12/2015 3:31:47 PM | A | CANC |
|
|
Need a fire alarm permit prior to the life safety inspection for the new Consulting Room at the Pharmacy and the two disable duct smoke detectors on the Mezzanine.
|
BLD15-00040
| FIRE-Final Inspection | 5/12/2015 | 5/12/2015 | 5/12/2015 3:29:51 PM | P | PASS |
|
|
life safety passed
|
FIR15-00036
| INSP-Sprinkler Rough-in | 5/12/2015 | 5/12/2015 | 5/12/2015 2:59:23 PM | P | PART |
|
|
OH/Hydro failed due to another contractor messing with a control valve. Previous corrections have been addressed and remaining piping can be covered.
|
NAF15-00016
| INSP-Final | 5/12/2015 | 5/12/2015 | 5/12/2015 2:32:14 PM | P | FAIL |
|
|
Cable did not release automatically and the gas did not shut off as required. Power to the lights did shunt.
|
FIR15-00010
| INSP-Final Inspection | 5/11/2015 | 5/12/2015 | 5/12/2015 10:42:05 AM | A | FAIL |
|
|
Two of the corridor fire doors released but did not latch. Also the strobe in the Breakroom did not activate with all of the other notification devices.
|
FIR14-00692
| INSP-Final Inspection | 5/11/2015 | 5/12/2015 | 5/12/2015 10:35:20 AM | A | CANC |
|
|
To be rescheduled with the 3rd floor re-inspection
|
FIR15-00150
| INSP-Alarm Testing | 5/5/2015 | 5/12/2015 | 5/12/2015 10:27:39 AM | A | FAIL |
|
|
Horn/strobe has been added to Laundry Room, smoke detectors have not been added to the Garden Room, knox box installed, map installed, set off notification and found that sync'ing is an issue with the sound and possibly with the strobes. I stopped the inspection of the horn/strobes as not to continue dicomfort of the tenants.
|
BLD15-01505
| FIRE-Final Inspection | 5/11/2015 | 5/12/2015 | 5/12/2015 9:21:14 AM | A | PASS |
|
|
life safety passed
|
NAF15-00016
| INSP-Sprinkler Rough-in/Hydro | 5/12/2015 | 5/12/2015 | 5/12/2015 12:00:00 AM | P | CANC |
|
|
Call prior to going Phone #: 2845608 >> Inspection requested via mobile web by Jordan Taylor
|
NAF15-00009
| INSP-Final | 5/12/2015 | 5/12/2015 | 5/12/2015 12:00:00 AM | P | PASS |
|
|
suppression system passed by inspector Troy Cobbley-per Troy Cobbley CAN
|