Inspections for the day of: Tuesday, May 12, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-00080 FIRE-Final Inspection5/11/20155/12/20155/12/2015 3:31:47 PMACANC
Need a fire alarm permit prior to the life safety inspection for the new Consulting Room at the Pharmacy and the two disable duct smoke detectors on the Mezzanine.
BLD15-00040 FIRE-Final Inspection5/12/20155/12/20155/12/2015 3:29:51 PMPPASS
life safety passed
FIR15-00036 INSP-Sprinkler Rough-in5/12/20155/12/20155/12/2015 2:59:23 PMPPART
OH/Hydro failed due to another contractor messing with a control valve. Previous corrections have been addressed and remaining piping can be covered.
NAF15-00016 INSP-Final5/12/20155/12/20155/12/2015 2:32:14 PMPFAIL
Cable did not release automatically and the gas did not shut off as required. Power to the lights did shunt.
FIR15-00010 INSP-Final Inspection5/11/20155/12/20155/12/2015 10:42:05 AMAFAIL
Two of the corridor fire doors released but did not latch. Also the strobe in the Breakroom did not activate with all of the other notification devices.
FIR14-00692 INSP-Final Inspection5/11/20155/12/20155/12/2015 10:35:20 AMACANC
To be rescheduled with the 3rd floor re-inspection
FIR15-00150 INSP-Alarm Testing5/5/20155/12/20155/12/2015 10:27:39 AMAFAIL
Horn/strobe has been added to Laundry Room, smoke detectors have not been added to the Garden Room, knox box installed, map installed, set off notification and found that sync'ing is an issue with the sound and possibly with the strobes. I stopped the inspection of the horn/strobes as not to continue dicomfort of the tenants.
BLD15-01505 FIRE-Final Inspection5/11/20155/12/20155/12/2015 9:21:14 AMAPASS
life safety passed
NAF15-00016 INSP-Sprinkler Rough-in/Hydro5/12/20155/12/20155/12/2015 12:00:00 AMPCANC
Call prior to going Phone #: 2845608 >> Inspection requested via mobile web by Jordan Taylor
NAF15-00009 INSP-Final5/12/20155/12/20155/12/2015 12:00:00 AMPPASS
suppression system passed by inspector Troy Cobbley-per Troy Cobbley CAN