Inspections for the day of: Tuesday, May 13, 2003.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-01584 FIRE-Final Inspection5/12/20035/13/20035/13/2003 12:00:00 AMAPASS
fire life safety finaled 5/13/2003 12:04:52 PM
FIR03-00128 INSP-Sprinkler Rough-in5/12/20035/13/20035/13/2003 12:00:00 AMAPASS
Fire sprinkler piping is OK to cover. I notified John Venchie with Debest Fire Protection that on the second floor in both apartments that the tenting on the pipe could be improved in a couple of locations. He stated that it would be taken care of. I also said the same thing to Frank, the superintendant 5/13/2003 9:17:19 AM 5/13/2003 9:20:22 AM
FIR02-00316 INSP-Final Inspection5/12/20035/13/20035/13/2003 12:00:00 AMAPART
The audio in the santuary does not meet the 75 db requirement. A temporary occupancy was given until the problem can be remedied. The temporary occupancy was given with Dave Millers permission 5/13/2003 10:27:45 AM
FIR03-00173 INSP-Final Inspection5/13/20035/13/20035/13/2003 12:00:00 AMAPASS
220 electrical service has been disconnected at the breaker box by Four Star Electric. The suppression system as installed is for duct and plenum coverage only. No appliances have been installed. The system operated correctly. I left a notice on the hood itself stating the hood is not to be used. I also spoke with Tom Greco, administrative pastor, about no appliances to be placed under the hood until a permit had been applied for and that the hood is not to be used until final inspections had been received. He agreed.
BLD02-00155 FIRE-Final Inspection5/13/20035/13/20035/13/2003 12:00:00 AMAPART
A temporary occupancy was given for fire alarm until the fire alarm permit is finaled. Life safety is OK other than the fire alarm
BLD02-02701 FIRE-Final Inspection5/13/20035/13/20035/13/2003 12:00:00 AMAFAIL
Repair the exit sign and the emergency light on the existing tenant side and provide approved door hardware on the restroom and tanning room doors
FIR02-00467 INSP-Final Inspection5/13/20035/13/20035/13/2003 12:00:00 AMAPASS
BLD03-00483 FIRE-Final Inspection5/13/20035/13/20035/13/2003 12:00:00 AMPPASS
fire life safety finaled 5/13/2003 1:49:37 PM
FIR03-00093 INSP-Supply line flush5/13/20035/13/20035/13/2003 12:00:00 AMPPASS
The inspection was not for a flush but for a cover of the underground. Piping is ok for cover 5/13/2003 3:03:53 PM
BLD03-00037 FIRE-Final Inspection5/12/20035/13/20035/13/2003 12:00:00 AMPFAIL
provide duct detectors for automatic shutdown of the hvac units. Paint curbing for fire dept access. provide ada hardware for pocket doors. Provide emergency light for second exit if exit is required 5/13/2003 4:23:41 PM
FIR03-00126 INSP-Sprinkler Rough-in/Hydro5/12/20035/13/20035/13/2003 12:00:00 AMPPASS
###-#### forest