BLD05-00517
| FIRE-Final Inspection | 5/13/2005 | 5/13/2005 | 5/13/2005 4:32:28 PM | P | FAIL |
|
|
Need to provide suite address numbers posted at main entrance.
|
BLD04-00159
| FIRE-Final Inspection | 5/13/2005 | 5/13/2005 | 5/13/2005 2:08:46 PM | P | FAIL |
|
|
Remote annunciators for duct smoke detection are not code approved. Remaining life safety issues still need review.
|
BLD04-00160
| FIRE-Final Inspection | 5/13/2005 | 5/13/2005 | 5/13/2005 2:01:48 PM | P | FAIL |
|
|
Smoke detectors did not shut down HVAC units upon activation. Post street address. Provide exit disharge light and test. Install fire extiguisher. Provide approved door hardware on pocket door at file room.
|
BLD04-00157
| FIRE-Final Inspection | 5/13/2005 | 5/13/2005 | 5/13/2005 1:57:25 PM | P | PART |
|
|
Pass inspection pending minor curb painting at short curb interval southeast main access roadway.
|
BLD05-00259
| FIRE-Final Inspection | 5/13/2005 | 5/13/2005 | 5/13/2005 10:58:08 AM | P | PASS |
|
|
Fire life safety finaled.
|
FIR04-00749
| INSP-Supply line flush | 5/10/2005 | 5/13/2005 | 5/13/2005 10:47:25 AM | A | PART |
|
|
Underground fire supply line and remote FDC flush satisfactory. Still need hydrostatic test performed.
|