ELE07-03503
| Conference | 5/13/2008 | 5/13/2008 | 5/13/2008 4:03:55 PM | P | DONE |
|
|
told contractor that permit would be ok to call for final when ready
|
ELE08-01182
| Final | 5/13/2008 | 5/13/2008 | 5/13/2008 3:55:06 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/13/2008 at 7:55:56 AM. ok to final
|
ELE08-01147
| Rough-In Permanent Service | 5/12/2008 | 5/13/2008 | 5/13/2008 2:20:41 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Candi Bahem called contractor, ric ok, p/s o/h rec ok
|
ELE08-01189
| Rough-In Permanent Service | 5/12/2008 | 5/13/2008 | 5/13/2008 1:53:02 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ric ok, p/s u/g n ok
|
ELE07-02686
| Final | 5/13/2008 | 5/13/2008 | 5/13/2008 12:59:42 PM | P | FAIL |
|
|
kirt Phone #: ###-#### afci would not trip with tester, has gfci recpts in circuit, will work on and recall
|
ELE08-01170
| Electrical Rough-In | 5/8/2008 | 5/13/2008 | 5/13/2008 10:42:11 AM | A | PASS |
|
|
bonding & cover inspection Phone #: ###-#### Internet Inspection Request from: Jari Rivers pool bonding ok, u/g ok to cover
|
ELE08-01214
| Permanent Service | 5/12/2008 | 5/13/2008 | 5/13/2008 10:34:15 AM | A | PASS |
|
|
clyde Note: please call 1/2 hr prior to inspection Phone #: ###-#### p/s exst meter pak n ok
|
ELE08-01213
| Permanent Service | 5/12/2008 | 5/13/2008 | 5/13/2008 10:14:30 AM | A | PASS |
|
|
clyde Note: please call 1/2 hr prior to inspection Phone #: ###-#### p/s exst meter pak n ok
|
ELE08-01212
| Permanent Service | 5/12/2008 | 5/13/2008 | 5/13/2008 9:48:00 AM | A | PASS |
|
|
clyde Note: please call 1/2 hr prior to inspection Phone #: ###-#### p/s exst meter pak n ok
|
ELE08-01211
| Permanent Service | 5/12/2008 | 5/13/2008 | 5/13/2008 9:19:21 AM | A | FAIL |
|
|
bucandi Phone #: ###-#### called, left correction notice on front fence, NEC 408.4 circuit directory shall be clear, concise, dierect, and explanatory, 312.5 all conductors entering enclosure shall have abrasion protection, 250.50 shall use water pipe for primary grounding electrode and augment with 2 ground rods
|
ELE08-01172
| Electrical Rough-In | 5/12/2008 | 5/13/2008 | 5/13/2008 8:48:03 AM | A | CANC |
|
|
call frist 15min ahead ###-#### dwight see conference
|
ELE08-01172
| Conference | 5/13/2008 | 5/13/2008 | 5/13/2008 8:47:45 AM | A | DONE |
|
|
call frist 15min ahead ###-#### dwight talked about outlet spacing, make-up, loading of circuits, arc-fault circuit interrupter for bedroom, breakers in panel
|
ELE07-03975
| Permanent Service | 5/13/2008 | 5/13/2008 | 5/13/2008 8:05:09 AM | A | PASS |
|
|
joe - ###-#### Note: ceiling inspection on the 2 editions in assist living p/s u/g n ok
|