Inspections for the day of: Tuesday, May 13, 2008.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03503 Conference5/13/20085/13/20085/13/2008 4:03:55 PMPDONE
told contractor that permit would be ok to call for final when ready
ELE08-01182 Final5/13/20085/13/20085/13/2008 3:55:06 PMPPASS
Scheduled by a contractor via Hello! on 5/13/2008 at 7:55:56 AM. ok to final
ELE08-01147 Rough-In Permanent Service5/12/20085/13/20085/13/2008 2:20:41 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Candi Bahem called contractor, ric ok, p/s o/h rec ok
ELE08-01189 Rough-In Permanent Service5/12/20085/13/20085/13/2008 1:53:02 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ric ok, p/s u/g n ok
ELE07-02686 Final5/13/20085/13/20085/13/2008 12:59:42 PMPFAIL
kirt Phone #: ###-#### afci would not trip with tester, has gfci recpts in circuit, will work on and recall
ELE08-01170 Electrical Rough-In5/8/20085/13/20085/13/2008 10:42:11 AMAPASS
bonding & cover inspection Phone #: ###-#### Internet Inspection Request from: Jari Rivers pool bonding ok, u/g ok to cover
ELE08-01214 Permanent Service5/12/20085/13/20085/13/2008 10:34:15 AMAPASS
clyde Note: please call 1/2 hr prior to inspection Phone #: ###-#### p/s exst meter pak n ok
ELE08-01213 Permanent Service5/12/20085/13/20085/13/2008 10:14:30 AMAPASS
clyde Note: please call 1/2 hr prior to inspection Phone #: ###-#### p/s exst meter pak n ok
ELE08-01212 Permanent Service5/12/20085/13/20085/13/2008 9:48:00 AMAPASS
clyde Note: please call 1/2 hr prior to inspection Phone #: ###-#### p/s exst meter pak n ok
ELE08-01211 Permanent Service5/12/20085/13/20085/13/2008 9:19:21 AMAFAIL
bucandi Phone #: ###-#### called, left correction notice on front fence, NEC 408.4 circuit directory shall be clear, concise, dierect, and explanatory, 312.5 all conductors entering enclosure shall have abrasion protection, 250.50 shall use water pipe for primary grounding electrode and augment with 2 ground rods
ELE08-01172 Electrical Rough-In5/12/20085/13/20085/13/2008 8:48:03 AMACANC
call frist 15min ahead ###-#### dwight see conference
ELE08-01172 Conference5/13/20085/13/20085/13/2008 8:47:45 AMADONE
call frist 15min ahead ###-#### dwight talked about outlet spacing, make-up, loading of circuits, arc-fault circuit interrupter for bedroom, breakers in panel
ELE07-03975 Permanent Service5/13/20085/13/20085/13/2008 8:05:09 AMAPASS
joe - ###-#### Note: ceiling inspection on the 2 editions in assist living p/s u/g n ok