ELE13-01097
| Electrical Rough-In | 5/10/2013 | 5/13/2013 | 5/13/2013 2:45:45 PM | P | NR |
|
|
Please inspect ceiling cover. Phone #: ###-#### >> Inspection requested via web by Navara Reardon Not ready for cover
|
ELE13-01132
| Rough-In Permanent Service | 5/13/2013 | 5/13/2013 | 5/13/2013 1:16:56 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson rough-in p/s u/g n ok
|
ELE13-01139
| Temporary Service | 5/13/2013 | 5/13/2013 | 5/13/2013 12:42:57 PM | P | PASS |
|
|
Correction done, t/s o/h n ok
|
ELE13-00969
| Final | 5/13/2013 | 5/13/2013 | 5/13/2013 12:17:38 PM | P | FAIL |
|
|
Shane Phone #: ###-#### 210.8(B)(5) All 15 and 20 ampere 120 volt receptacles within 6ft. of an sink require GFCI protection
|
ELE12-00802
| Conference | 5/9/2013 | 5/13/2013 | 5/13/2013 9:51:23 AM | A | DONE |
|
|
Greg Critchfield is contact ###-####. thank you. Phone #: ###-#### >> Inspection requested via web by Debby Ellis Discussed requirements for conductor separation between life safety and critical branch conductors
|
ELE13-01143
| Temporary Service | 5/12/2013 | 5/13/2013 | 5/13/2013 8:23:03 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Kevin Burke t/s u/g n ok
|
ELE13-01038
| Electrical Rough-In | 5/10/2013 | 5/13/2013 | 5/13/2013 8:03:13 AM | A | PASS |
|
|
the restroom wall need a cover inspection call corey with questions thanks Phone #: ###-#### >> Inspection requested via web by Don Lustig rough-in ok cover
|