Inspections for the day of: Monday, May 13, 2013.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01097 Electrical Rough-In5/10/20135/13/20135/13/2013 2:45:45 PMPNR
Please inspect ceiling cover. Phone #: ###-#### >> Inspection requested via web by Navara Reardon Not ready for cover
ELE13-01132 Rough-In Permanent Service5/13/20135/13/20135/13/2013 1:16:56 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson rough-in p/s u/g n ok
ELE13-01139 Temporary Service5/13/20135/13/20135/13/2013 12:42:57 PMPPASS
Correction done, t/s o/h n ok
ELE13-00969 Final5/13/20135/13/20135/13/2013 12:17:38 PMPFAIL
Shane Phone #: ###-#### 210.8(B)(5) All 15 and 20 ampere 120 volt receptacles within 6ft. of an sink require GFCI protection
ELE12-00802 Conference5/9/20135/13/20135/13/2013 9:51:23 AMADONE
Greg Critchfield is contact ###-####. thank you. Phone #: ###-#### >> Inspection requested via web by Debby Ellis Discussed requirements for conductor separation between life safety and critical branch conductors
ELE13-01143 Temporary Service5/12/20135/13/20135/13/2013 8:23:03 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Kevin Burke t/s u/g n ok
ELE13-01038 Electrical Rough-In5/10/20135/13/20135/13/2013 8:03:13 AMAPASS
the restroom wall need a cover inspection call corey with questions thanks
Phone #: ###-#### >> Inspection requested via web by Don Lustig rough-in ok cover