Inspections for the day of: Tuesday, May 13, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00952 Permanent Service5/13/20145/13/20145/13/2014 3:51:37 PMPFAIL
Web Robertson Phone #: ###-#### Due to modifications new code violations exist. 110.26- Minimum work platform 30" wide and 36" deep.
240.24(A)- Each circuit breaker that can be installed shall be below 6'7".
250.64(B)- Where exposed a #4 minimum copper grounding electrode conductor shall be installed where subject to physical damage.
250.56- Ground rods shall be installed a minimum of 6' apart.
230.24(A)- Service mast shall clear short overhang portion of roof by minimum of 18".
Tried to contact owner 2 times. sounded like voicemail was available on 2nd call but not sure if operational .
ELE14-01220 Electrical Rough-In5/13/20145/13/20145/13/2014 3:02:47 PMPPASS
Go thru gate on side of house to back yard any questions pleas call shaun ###-#### thanks Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman Garage addition to back of house garage. Rough in ok cover
ELE14-00952 Final5/13/20145/13/20145/13/2014 2:09:02 PMPCANC
Web Robertson Phone #: ###-#### Needed permenant service inspection.
ELE14-01210 Permanent Service5/13/20145/13/20145/13/2014 1:44:28 PMPNH
CONTACT: CODY CANNON Phone #: ###-#### >> Inspection requested via web by Deb Gooden House locked no answer at number provided.
ELE14-01135 Final5/12/20145/13/20145/13/2014 1:15:45 PMPPASS
The owner will meet you there to open the door. Please call me 20 minutes prior so I can make sure we can coordinate. Eddy at ###-####. Thanks Phone #: ###-#### >> Inspection requested via web by Eddy Udry p/s o/h rec ok
ELE14-00261 Final5/13/20145/13/20145/13/2014 12:45:19 PMPPASS
Phone #: ###-#### >> Inspection requested via web by John VanZandt Final ok
ELE14-01202 Electrical Rough-In5/12/20145/13/20145/13/2014 10:27:36 AMAPASS
I would like a cover inspection they turned one big office into two offices we added outlets in the new wall and added 2 double switches for the two offices. The building will be open all day go in the front doors first door on left Phone #: ###-#### >> Inspection requested via web by Kevin Oderkirk Space 180 being split new office north end. Wall rough in ok cover
ELE14-01219 Permanent Service5/13/20145/13/20145/13/2014 9:56:58 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack
p/s o/h n ok
ELE14-01219 Electrical Rough-In5/13/20145/13/20145/13/2014 9:56:57 AMPFAIL
Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack 400.5(A)- #8 SEOOW 3 current carrying conductor cord max ampacity 35 amps, 50 amp over current installed
ELE14-01219 Electrical Rough-In5/13/20145/13/20145/13/2014 9:56:31 AMPFAIL
Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack 400.5(A)- # 8 SEOOW 3 current carrying conductor cord max ampacity 35 amps, 50 amp over current installed.
ELE14-01134 Final5/12/20145/13/20145/13/2014 9:23:12 AMANR
troy Phone #: ###-#### Existing electrical boxes open, whips not terminated, GFCI protection needed for all 120 receptical outlets.
ELE12-02153 Final5/12/20145/13/20145/13/2014 8:52:36 AMAPASS
I looked back at my records and they indicated this was not a service change. If I remember right you came and looked at the trench for some shed power. Sorry its been so long and I am not much help. Phone #: ###-#### >> Inspection requested via web by Craig Korell Final ok