BLD14-01201
| FIRE-Final Inspection | 5/9/2014 | 5/13/2014 | 5/13/2014 3:33:13 PM | P | FAIL |
|
|
Provide smoke alarms as per the approved plans. Provide fire extinguishers on stair landingas discussed.
|
BLD14-01179
| FIRE-Final Inspection | 5/9/2014 | 5/13/2014 | 5/13/2014 3:31:48 PM | P | FAIL |
|
|
Provide smoke alarms as per the approved plans. Provide fire extiinguishers as discussed on the stair landings or in each apartment as discussed.
|
FIR14-00137
| INSP-Sprinkler Rough-in | 5/12/2014 | 5/13/2014 | 5/13/2014 2:00:28 PM | A | PASS |
|
|
See the city approved plans for locations where piping can be covered
|
FIR14-00199
| INSP-Final Inspection | 5/8/2014 | 5/13/2014 | 5/13/2014 11:43:02 AM | A | FAIL |
|
|
All alarm audible devices must sync. NFPA 7218.4.2.4, All visual devices must sync NFPA 7218.5.5.4.2, All audible alarm devices shall use "temporal tone" NFPA 7218.4.2.1, All areas/notification shall activate upon alarm IFC907.6, Provide fire alarm notification devices through out all required areas as per IFC 907 and installed per NFPA 72. If wanted provide upgrade agreement, as discussed, to Scott Arellano for review.
|
BLD14-00873
| FIRE-Final Inspection | 5/12/2014 | 5/13/2014 | 5/13/2014 8:20:03 AM | A | PASS |
|
|
life safety passed
|