Inspections for the day of: Tuesday, May 13, 2014.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-01201 FIRE-Final Inspection5/9/20145/13/20145/13/2014 3:33:13 PMPFAIL
Provide smoke alarms as per the approved plans. Provide fire extinguishers on stair landingas discussed.
BLD14-01179 FIRE-Final Inspection5/9/20145/13/20145/13/2014 3:31:48 PMPFAIL
Provide smoke alarms as per the approved plans. Provide fire extiinguishers as discussed on the stair landings or in each apartment as discussed.
FIR14-00137 INSP-Sprinkler Rough-in5/12/20145/13/20145/13/2014 2:00:28 PMAPASS
See the city approved plans for locations where piping can be covered
FIR14-00199 INSP-Final Inspection5/8/20145/13/20145/13/2014 11:43:02 AMAFAIL
All alarm audible devices must sync. NFPA 7218.4.2.4, All visual devices must sync NFPA 7218.5.5.4.2, All audible alarm devices shall use "temporal tone" NFPA 7218.4.2.1, All areas/notification shall activate upon alarm IFC907.6, Provide fire alarm notification devices through out all required areas as per IFC 907 and installed per NFPA 72. If wanted provide upgrade agreement, as discussed, to Scott Arellano for review.
BLD14-00873 FIRE-Final Inspection5/12/20145/13/20145/13/2014 8:20:03 AMAPASS
life safety passed