FIR15-00113
| INSP-Final Inspection | 5/13/2015 | 5/13/2015 | 5/13/2015 4:31:00 PM | P | PASS |
|
|
Fire alarm functional test pass. Scope of work complete. Permit finaled.
|
BLD14-03560
| FIRE-Final Inspection | 5/13/2015 | 5/13/2015 | 5/13/2015 4:29:57 PM | P | PASS |
|
|
Fire life safety pass.
|
FIR15-00181
| INSP-Final Inspection | 5/12/2015 | 5/13/2015 | 5/13/2015 4:25:45 PM | P | PASS |
|
|
Hood suppression system functional test pass. Scope of work completed. Permit Finaled.
|
FIR15-00079
| INSP-Final Inspection | 5/12/2015 | 5/13/2015 | 5/13/2015 4:17:01 PM | P | PASS |
|
|
Scope of work completed satisfactory. Verified cooler drop and electrical room drop.
|
BLD15-01450
| FIRE-Conference | 5/13/2015 | 5/13/2015 | 5/13/2015 2:01:21 PM | P | DONE |
|
|
Fire conference to discuss whether sprinkler heads needed to be replaced. Spacing was ok but three heads are painted. Advised to replace those three heads, keeping same response (standard) type.
|
FIR15-00248
| INSP-Final Inspection | 5/13/2015 | 5/13/2015 | 5/13/2015 1:28:23 PM | P | PASS |
|
|
Scope of work completed satisfactory. Permit finaled.
|
BLD15-01544
| FIRE-Final Inspection | 5/12/2015 | 5/13/2015 | 5/13/2015 1:04:13 PM | A | FAIL |
|
|
Life Safety Fail, missing suite number identification and recessed fire extinguisher cabinet and extinguisher as per plan. Emergency lights need to be either repaired or removed.
|
FIR15-00177
| INSP-Sprinkler Rough-in/Hydro | 5/12/2015 | 5/13/2015 | 5/13/2015 10:49:49 AM | A | PASS |
|
|
Underground hydro pass. System did loose 5 psig over 2 hours which is in the allowable ranger per code.
|
BLD14-01545
| FIRE-Final Inspection | 5/12/2015 | 5/13/2015 | 5/13/2015 9:37:14 AM | A | PASS |
|
|
Fire life safety pass.
|
BLD14-03213
| FIRE-Final Inspection | 5/12/2015 | 5/13/2015 | 5/13/2015 8:18:48 AM | A | NR |
|
|
Not ready for life safety inspection. An issued fire alarm permit FIR15-00144 needs to be finaled prior.
|