FIR19-00270
| INSP-Sprinkler Rough-in | 5/10/2019 | 5/13/2019 | 5/13/2019 3:49:15 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in scope of work complete, approved for cover.
Tom Phone #: ###-####
|
FIR18-00610
| INSP-Sprinkler Rough-in | 5/13/2019 | 5/13/2019 | 5/13/2019 3:34:10 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping in common corridors and elevator lobby on levels 3 and 4 complete, approved for cover.
Mike Phone #: ###-####
|
BLD19-00961
| FIRE-Final Inspection | 5/13/2019 | 5/13/2019 | 5/13/2019 3:09:17 PM | P | PASS |
|
|
Final life fire safety inspection for area of work complete.
Mark Phone #: ###-####
|
BLD18-00944
| FIRE-Final Inspection | 5/10/2019 | 5/13/2019 | 5/13/2019 2:45:39 PM | P | CANC |
|
|
GC noticed that the FIR permit for sprinklers was still in issued status, GC will coordinate with the sprinkler contractor to get both inspections completed, this request is cancelled per conversation with point of contact.
Kirt Phone #: ###-####
|
FIR19-00111
| INSP-Sprinkler Rough-in | 5/9/2019 | 5/13/2019 | 5/13/2019 2:40:10 PM | P | PART |
|
|
Rough to cover inspection for levels 1 and 2 complete, levels 1 and 2 approved for cover. Level 3 rough in inspection complete, tenting/insulation to be installed at a later date, an inspection for tenting is required before cover can be approved, level 3 cover is not approved as of this inspection.
Contact Noemi Carrero ###-#### 30 Min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00323
| INSP-Final Inspection | 5/13/2019 | 5/13/2019 | 5/13/2019 1:50:31 PM | P | PASS |
|
|
Final fire alarm inspection complete.
Phone #: ###-#### Inspection requested via web by Matt Casey
|
FIR18-00565
| INSP-Final Inspection | 5/10/2019 | 5/13/2019 | 5/13/2019 1:49:54 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
Johnathon Phone #: ###-####
|
BLD17-03885
| FIRE-Conference | 5/13/2019 | 5/13/2019 | 5/13/2019 11:52:14 AM | P | DONE |
|
|
Wall mounted post indicator is to high above finish grade, maximum allowable elevation above finish floor needs to be 48 inches or less per conversation with Ron Johnson with Boise Fire. Manhole cover will be placed over sewer clean-out pit prior to final occupancy.
|
FIR18-00501
| INSP-Final Inspection | 5/10/2019 | 5/13/2019 | 5/13/2019 11:50:07 AM | P | FAIL |
|
|
Provide dry sidewall under combustible over-hang above west exit. Replace upright fire sprinkler head that was painted in the south room behind habitat exhibit. Replace exposed CPVC to steel pipe. Change upright head in restroom to the required pendant head. Replace pendant head that is in FACP room with an upright head as discussed.
George Jess is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD17-03885
| FIRE-Final Inspection | 5/13/2019 | 5/13/2019 | 5/13/2019 11:46:57 AM | P | CANC |
|
|
Request was for a conference, this request is cancelled.
Please coordinate with fire suppression and alarm. building D7 Phone #: ###-#### Inspection requested via web by Brandon Reynolds
|
FIR19-00257
| INSP-Final Inspection | 5/8/2019 | 5/13/2019 | 5/13/2019 11:45:43 AM | P | PASS |
|
|
Final fire alarm inspection complete.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD19-01357
| FIRE-Final Inspection | 5/10/2019 | 5/13/2019 | 5/13/2019 9:47:30 AM | A | PASS |
|
|
Final life fire safety inspection for permit area complete.
Sharm Phone #: ###-####-call 30 minutes prior
|
BLD18-04526
| FIRE-Final Inspection | 5/10/2019 | 5/13/2019 | 5/13/2019 9:23:43 AM | A | FAIL |
|
|
Provide emergency lighting for exit discharge above northeast exterior exit. Install single action door hardware on restroom that has round type door hardware. Provide maximum occupancy placard.
Rick Phone #: ###-####
|
FIR19-00077
| INSP-Sprinkler Rough-in | 5/10/2019 | 5/13/2019 | 5/13/2019 9:03:29 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, notated city approved drawings with red ink areas approved for cover.
Tom Phone #: ###-####
|
FIR19-00263
| INSP-Sprinkler Rough-in | 5/10/2019 | 5/13/2019 | 5/13/2019 12:00:00 AM | P | PASS |
|
|
OK to cover area "A" only, notes made to plan mod #1 plan on site.***MAS**
Colton Cox is the contact. This rough-in is for section A of the building. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus
|