Inspections for the day of: Tuesday, May 14, 2002.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE01-04140 Electrical Rough-In5/13/20025/14/20025/14/2002 12:00:00 AMAPART
###-#### JUDITH CALL 1ST ###-#### STEVE
sofits ok 5/14/2002 12:59:11 PM
ELE02-01339 Permanent Service5/13/20025/14/20025/14/2002 12:00:00 AMAPASS
andy ###-#### per ser
P/S U/G R Ok 5/14/2002 10:26:49 AM
ELE02-01420 Final5/13/20025/14/20025/14/2002 12:00:00 AMANR
###-####
R/I Ok 5/14/2002 12:14:32 PM
ELE02-00886 Final5/13/20025/14/20025/14/2002 12:00:00 AMAFAIL
###-#### ROD
In use covers 5/14/2002 11:03:13 AM
ELE02-00815 Rough-In Permanent Service5/13/20025/14/20025/14/2002 12:00:00 AMAPASS
###-#### JOHN
garage r/i 5/14/2002 11:29:42 AM
ELE02-00876 Final5/14/20025/14/20025/14/2002 12:00:00 AMPPASS
###-####
ELE02-01432 Electrical Rough-In5/14/20025/14/20025/14/2002 12:00:00 AMPPART
r/i pat ###-####
Walls Ok 5/14/2002 5:57:43 PM
ELE02-00287 Final5/14/20025/14/20025/14/2002 12:00:00 AMPNR
fn insp- allen ###-####
counters not complete
peninsular counter will require a recep.
downstairs bedroom requires arc fault
fixture above tub/shower not wet location 5/14/2002 4:14:38 PM
ELE02-00910 Final5/14/20025/14/20025/14/2002 12:00:00 AMPPASS
fn insp-lynn ###-####
finaled with survey to make lighting outlet box in bathroom accessible. 5/14/2002 5:34:31 PM
ELE02-01417 Temporary Service5/14/20025/14/20025/14/2002 12:00:00 AMPFAIL
EMMETT ###-####